Form I-PDH-V, P/N 211409R2, Page 1

Applies to:

PREEVA

®

Indoor, Power-Vented

Heater Model PDH

Venting Instructions

Form I-PDH-V

General

Venting

Requirements

Verify that the label near the

vent outlet on the heater

matches this label.

Power-Vent

Indoor

Model PDH

AG

EN

CY

PROCE

SS

ST

A

R

T-

U

P

PR

ODUCT

C

U

ST

O

M

ER

WAR

RA

NT

Y

CO

NVERGENT

QU

ALITY SYSTE

M

CQS

CQS

This manual applies only to venting instructions and must be used with the Model PDH

installation manual, Form I-PDH/SDH/PEH/SHH/PXH. Both manuals are shipped with

the heater. If either manual is missing, contact your distributor before beginning instal-

lation. The venting instructions in this manual apply only to PREEVA

®

Model PDH.

Model PDH heaters are certified as Category III appliances.

WARNING

Each heater requires its own individual vent pipe run and vent cap.

Manifolding of vent runs can cause recirculation of combustion

products into the building. Failure to comply could result in severe

personal injury or death and/or property damage.

Venting must be in accordance with local codes and the National Fuel Gas Code NFPA

54 / ANSI Z223.1 or CAN/CSA B149.1 Natural Gas and Propane Installation Code.

Local requirements supersede national requirements.
This power-vented heater is designed to operate safely and efficiently with either a

horizontal or vertical vent. Comply with the specific requirements and instructions.
If this heater is replacing an existing heater, be sure that the vent is sized properly for

the heater being installed and that the existing vent is in good condition. A properly

sized vent system is required for safe operation of the heater. An improperly sized vent

system can cause unsafe conditions and/or create condensation. Do not vent into an

existing gravity vent or chimney.
Installation should be done by a qualified agency in accordance with these instructions.

The qualified service agency installing this system is responsible for the installation.

1. Type of Vent Pipe

A commercial/industrial installation may have either a horizontal or a vertical vent run

using one of the types of vent pipe listed.

Horizontal

Vent Run

Vent pipe approved to UL Std 1738 for a Category III appliance,

OR

Appropriately sealed 26-gauge or heavier galvanized steel or

equivalent single-wall pipe

Vertical

Vent Run

Vent pipe approved to UL Std 1738 for a Category III appliance,

OR

Appropriately sealed 26-gauge or heavier galvanized steel or

equivalent single-wall pipe

OR, if at least 75% of the equivalent length of the vent run is vertical

Vent Terminal

Section

Both horizontal and vertical vent terminal section must be

double-wall (Type B) vent pipe

201214