Blower speed, Fixed torque ecm motor, Unit. for unit weights, see – Reznor P8SE Unit Installation Manual User Manual

Page 9: Reinforce, Caution

Advertising
background image

9

blower Speed

caution:

to avoid personal injury or property damage,

make certain that the motor leads cannot

come into contact with any uninsulated metal

components of the unit.

The blower speed is preset at the factory for operation

at the same speed for heating and cooling. These

factory settings are listed in

Table 5

.For optimum system

performance and comfort, it may be necessary to change

the factory set speed.

Fixed Torque ECM Motor

1. Shut off all electrical power to the unit and remove

the blower panel. Locate the orange and red wires

terminated to the blower motor.

note: The orange wire

controls cooling operation while the red wire controls

heating operation.

2. Verify the required speed from the airflow data found

in

Table 5

. Place appropriate wire on the correct motor

speed tap for the required airflow point.

table 3. thermostat Wire gauge

tHerMoStat

Wire gauge

recoMMended t-Stat Wire

lengtH (unit to t-Stat)

2-Wire

(Heating)

5-Wire

(Heating/cooling)

24

55

25

22

90

45

20

140

70

18

225

110

kW/H

btu/H

5

17,060

8

27,297

9

30,709

10

34,121

15

51,182

20

68,242

table 4. kW & btu/h ratings

Model

nuMber

P8Se -

eXternal Static PreSSure droP - incHeS Water coluMn

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

X36

Tap T1**

1091 28.96 1031 30.64

995 31.75

929 34.01

871 36.27

774

41

704

45

629

50

Tap T2*

1296 24.38 1244 25.40 1169 27.03 1153 27.40 1089 29.01 1030 30.67

961 32.88

863 36.61

Tap T3

1525 20.72 1499 21.08 1448 21.82 1391 22.71 1338 23.61 1264 25.00 1221 25.88 1159 27.26

Tap T4

1641 19.25 1590 19.87 1543 20.48 1489 21.22 1444 21.88 1386 22.80 1345 23.49 1285 24.59

Tap T5

1791 17.64 1740 18.16 1659 19.04 1610 19.62 1555 20.32 1521 20.77 1467 21.54 1414 22.34

X48

Tap T1**

1264 25.00 1183 26.71 1126 28.06 1051 30.06

954 33.12

848 37.26

774 40.82

716 44.13

Tap T2

1462 21.61 1397 22.62 1322 23.90 1240 25.48 1181 26.75 1133 27.89 1006 31.41

888 35.58

Tap T3*

1776 17.79 1717 18.40 1654 19.10 1573 20.09 1533 20.61 1484 21.29 1422 22.22 1369 23.08

Tap T4

2127 14.85 2037 15.51 2008 15.73 1957 16.14 1865 16.94 1801 17.54 1743 18.13 1690 18.69

Tap T5

2419 13.06 2355 13.42 2311 13.67 2267 13.94 2194 14.40 2150 14.69 2085 15.15 2027 15.59

X60

Tap T1**

1209 26.13 1145 27.59 1106 28.57 1020 30.97

928 34.05

843 37.48

776 40.71

709 44.56

Tap T2

1629 19.39 1550 20.38 1479 21.36 1435 22.02 1369 23.08 1300 24.30 1244 25.40 1139 27.74

Tap T3*

1847 17.11 1800 17.55 1718 18.39 1668 18.94 1611 19.61 1556 20.30 1497 21.10 1449 21.80

Tap T4

2128 14.85 2059 15.34 1992 15.86 1961 16.11 1887 16.74 1828 17.28 1779 17.76 1718 18.39

Tap T5

2500 12.64 2444 12.93 2417 13.07 2345 13.47 2285 13.83 2228 14.18 2172 14.55 2109 14.98

noteS:

* Denotes factory set cooling speed
** Denotes factory set electric heating speed
Calculations made using 10kW heater kit.

table 5. P86e Series blower curves