Electrical data – Reznor Q6SP Unit Installation Manual User Manual

Page 17

Advertising
background image

17

ElEctrIcal Data

Model

number

Q6sP-

(see notes 2 & 3)

nominal

unit

Voltage

(see note 1)

High

static

Kit #

compressors

outdoor

motors

(2) ea.

Indoor Motor

(see note 4)

total

unit

rla

unit only

circuit

Qty

rla

lra

Fla

Hp

Fla

rla

Mca

MoP

Factory unit Electrical Data

-090Ca

208 - 230 V

Factory Std.

2 ea.

13.1

83.1

2.3

1

3.2 - 3.1

34.1

37 - 37

50 - 50

-090Da

460 V

2 ea.

6.1

41

1.2

1.5

16.1

18

20

-120Ca

208 - 230 V

Factory Std.

2 ea.

15.6

110

2.3

1.5

4.4 - 4.2

40.3

44 - 44

50 - 50

-120Da

460 V

2 ea.

7.8

52

1.2

2.1

20.1

22

25

Medium & High static Drive Electrical Data

-090Ca

208 - 230 V

921646

2 ea.

13.1

83.1

2.3

1.5

4.4 - 4.2

35.3

39 - 38

50 - 50

-090Da

460 V

2 ea.

6.1

41

1.2

2.1

16.7

18

20

-090Ca

208 - 230 V

921647

2 ea.

13.1

83.1

2.3

2

6.0 - 5.8

36.9

40 - 40

50 - 50

-090Da

460 V

2 ea.

6.1

41

1.2

2.9

17.5

19

25

-120Ca

208 - 230 V

921645

2 ea.

15.6

110

2.3

2

6.0 - 5.8

41.9

46 - 46

60 - 60

-120Da

460 V

2 ea.

7.8

52

1.2

2.9

20.9

23

30

table 2a. Q6sP Electrical Data - Multiple supply circuits / unit only

H5HK

Heater Kit

Model #

(see note 6)

Electric Heat Kit (Field Installed with Multiple circuit Kit # 917468)

Electrical Data table - Heater onlY

nominal

Heater

kW

line

Voltage

actual
Heater

kW

Heater amps

(line)

Heater only circuit

Mca

MoP

009Q-01

9

208 / 240

6.76 / 9.0

18.76 / 21.65

23.5 / 27.1

25 / 30

018Q-11

18

208 / 240

13.07 / 17.4

36.28 / 41.86

45.3 / 52.3

50 / 60

030Q-22

30

208 / 240

21.63 / 28.80

60.0 / 69.3

75.1 / 86.6

80 / 90

035Q-22

35

208 / 240

26.1 / 34.8

72.55 / 83.72

90.7 / 104.6

100 / 110

009S-01

9

480

9.9

11.91

14.9

15

018S-01

18

480

18

21.65

27.1

30

030S-01

30

480

28.8

34.64

43.3

45

035S-01

35

480

34.8

41.86

52.3

60

notEs:
1) To achieve the rated unit performance, unit voltage should be within 2% of nominal.
2) For C series units:

Nominal Unit Input Voltage = 208-230 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 187V
Maximum allowed voltage = 253V

3) For D series units:

Nominal Unit Input Voltage = 460 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 414V
Maximum allowed voltage = 506V

4) Indoor Motors meet 2010 DOE requirements (Premium Efficient)
5) Refer to High Static Drive Kit Installation Instructions for additional information
6) Refer to H5HK Kit Installation Instructions for additional information
7) FLA = Full Load Amps

MCA = Minimum Circuit Ampacity

RLA = Rated Load Amps

MOP = Maximum Over-Current Protection

LRA = Locked Rotor Amps

8) Refer to table 3 for single circuit MCA/MOP data

table 2b. H5HK Electrical Data - Multiple supply circuits