Reznor P6SP Option - Installation - Heater Kit User Manual

Installation instructions, Warning, 3 phase electrical heater kits

Advertising
background image

Installation Instructions

The 3 Pole Dual Circuit Adaptor Kit is designed for use in
all 6 through 10 Ton Single Package Air-Conditioner and
Heat Pump products when installing electric heat modules.
Factory single electrical circuit supply connections may be
converted to dual (Cooling and Heating) electrical supply
connections if desired.

NOTE: This kit is specifi cally designed for Cooling
Operation only. (Circuit “A”)

See the unit rating label for proper high voltage wiring
requirements. Over-current protection must be provided at
the branch circuit distribution panel and sized as shown on
the unit rating label and according to the National Electrical
Code (ANSI/NFPA 70), Canadian Electrical Code Part 1
(CSA C.22.1), and all applicable local codes.

NOTE: Circuit Breakers installed in the unit with the
addition of heater kits are for short circuit protection
of the internal heater element circuit wiring and NOT
to serve as a disconnect. The circuit breakers DO
NOT provide over-current protection of the supply
wiring.

KIT CONTENTS

1. 632348 – 3-pole terminal block

2. 632575 – terminal block insulator plate

3. 600004 – #10 1” long screws (2 ea)

4. 631915 – insulated, ¼” female quick connect terminal,

blue, for wire gauges 14-16 (3 ea)

5. 631764 – insulated, ¼” female quick connect terminal,

red, for wire gauges 18-22 (3 ea)

6. 6 ea. zip ties & 12 ea. push ties

INSTALLATION SEQUENCE

WARNING:

To avoid risk of electrical shock, personal
injury, or death, disconnect electrical
power to the unit before performing any
maintenance or service. The unit may have
more than one electric power supply.

3 Pole Dual Electrical Circuit Adaptor Kit #917468

3 Phase Electrical Heater Kits

INTRODUCTION

These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of
heating and/or air conditioning appliances. Before beginning the installation, read these instructions thoroughly and
follow all warnings and cautions in the instructions and on the unit. Improper installation, service, adjustment, or
maintenance can cause explosion, fi re, electrical shock, or other conditions which may result in personal injury or
property damage.

Electric

Element

Mounting

Location

3 Pole

Insulator
Plate

Dual

Circuit

Adaptor

Figure 1. Terminal Board Location

Advertising