Reznor Q6SP Option - Installation - Enthalpy Sensor - Light Commercial User Manual

Warning, Installation instructions

Advertising
background image

Solid - State Enthalpy Sensor - C7400A

Accessories - Commercial Package Equipment

IMPORTANT SAFETY INFORMATION

INSTALLER: Please read all instructions before servicing this
equipment. Pay attention to all safety warnings and any other
special notes. Safety markings are used frequently throughout
these instructions to designate a degree or level of seriousness
and should not be ignored.

WARNING - Indicates a potentially hazardous situation that if
not avoided, could result in personal injury or death.

CAUTION - Indicates a potentially hazardous situation that if
not avoided, may result in minor or moderate injury or property
damage.

WARNING:

This kit is to be installed by a qualified service
technician in accordance with these instructions and
all codes having jurisdiction. Failure to follow these
instructions could result in serious injury, property
damage, or death.

WARNING:

All electrical wiring must comply with the latest
edition of the National Electrical Code ANSI/NFPA 70.

These instructions are primarily intended to assist qualified

individuals experienced in the proper installation of this
appliance. Some local codes require licensed installation/
service personnel for this type of equipment.

Read these instructions and those which accompany the
Solid-State Enthalpy control in their entirety before proceeding
with the installation of this control kit.

AbOUT ThE ENThAlPY SENSOR

This Solid-State Differential Enthalpy Control kit can be used
for all Nordyne economizer applications. The C7400A Enthalpy
Sensor is only used with economizer logic modules having the
A,B,C, & D performance curves. This second C7400A control is
used to achieve maximum system efficiencies over the standard
single enthalpy control application. The differential enthalpy
control system compares the temperature and humidity of
the outside air to that of the building return air and allows the
economizer to adjust position to ensure the lowest enthalpy air
is used for cooling.

DIFFERENTIAl ENThAlPY CONTROl

1. SET UNIT INDOOR ThERMOSTAT TO ThE “OFF”

POSITION.

2. DISCONNECT All ElECTRICAl POWER TO ThE UNIT.

3. The second C7400A controller is used for return air sensing

and should be mounted in the return air duct as far from the
outdoor air sensor as possible.

IMPORTANT NOTES:

The C7400 sensor can be mounted in any position.
however, the sensor must be installed where it is exposed
to freely circulating air, but protected from rain, snow, and
direct sunlight.

The C7400 sensor is designed to operate in 500 ft. /
minimum airflow.

Connect the blue wire to the “S” terminal and the Violet
wire to the “+” terminal of the C7400A control.

If needed, see the sensor mounting section for additional
information.

4. Partial removal of economizer may be required for wire routing

purposes.

5. Remove the 7/8” K.O. located on the lower right side of

economizer panel, insert wire grommet provided in kit, then
route wires from the second sensor out through grommet and
along existing wiring harness. Wire tie as required to keep
away from vane travel.

6. Remove the 620 Ohm resistor across SR and (+) on the

W7459A or W7212A logic module and connect additional
C7400 for differential operation.

IMPORTANT! Connect the blue wire to the “SR” terminal

and the Violet wire to the “+” terminal of the logic module.

7. The enthalpy control setpoint scale markings located on

the W7459A & W7212A are A, B, C, and D. They are field
selectable and are used for single enthalpy control only.

IMPORTANT! Turn the setpoint potentiometer fully

clockwise to the “D” setting for Differential Enthalpy
control. The economizer will select the air with lower
enthalpy for cooling. i.e. If outdoor air has lower enthalpy
than return air, then the outdoor air damper will be opened
to bring in outdoor air for free cooling.

8. Replace all panels.

9. Reconnect electrical power to the unit and check economizer

for proper operation.