Reznor R6GP Option - Installation - Flue Exhaust Extension User Manual

Installation instructions, Warning, Flue exhaust kit

Advertising
background image

Installation Instructions

Flue Exhaust Kit

These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of
heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this
type of equipment. All installations must be in accordance with these instructions and with all applicable national
and local codes and standards. Before beginning the installation, read these instructions thoroughly and follow all
warnings and cautions in the instructions and on the unit. WARNING indicates a potentially hazardous situation that
if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if
not avoided, may result in minor or moderate injury or property damage.

INTRODUCTION

This kit is for use on outdoor gas fi red/AC units for use
in commercial applications. The applicable units for
installation are R6(GN,GP) models with cooling capacities
ranging from 6 Tons to 10 Tons. The components of this kit
make it possible to vent the products of gas combustion
to a height of two feet above the top of the unit.

Installation Instructions

1

Telescoping Flue Body

1

Start Collar, 5 inch

1

Elbow, 90°, 5 inch

1

Flue Support Bracket

1

Screw, #10 X 1/2 inch

15

Bolt, #18 X 1-3/4 inch

1

Hex Nut, #18

1

Lock Washer

1

Table 1. Flue Exhaust Kit Contents

Table 2. Flue Body Length

Figure 1. Flue body Length

INSTALLATION OF FLUE EXHAUST KIT

WARNING

Shut off the gas supply at the manual gas
shutoff valve, before disconnecting the
electrical power. A fi re or explosion may
result causing property damage, personal
injury or loss of life. Failure to follow the
safety warnings exactly could result in
serious injury, death or property damage.

1. Shut off gas supply and disconnect electrical power
to the unit.

2. Use Table 2 and Figure 1 to determine the proper
length of fl ue body for your installation.

Unit Height (in.)

X (in.)

43.5

1.75

55.25

6.25

3. Use three of the self drilling screws to secure the

inner and outer fl ue sections together. As seen in
Figure 2, the channel in the outer fl ue section is
provided allow a consistent screw pattern around
the circumference of the fl ue body. The screws must
be spaced at even intervals (120 degrees apart)
around the fl ue body.

X

Advertising