Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 14

Advertising
background image

14

P6SP-090*

MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

3411

3228

3136

3043

RPM

1053

1025

1013

1000

kW

1.98

1.78

1.68

1.58

0.9

CFM

3309

3131

3005

2878

RPM

1065

1039

1022

1005

kW

1.94

1.75

1.59

1.43

1.0

CFM

3410

3221

3031

2851

2670

RPM

1110

1083

1055

1032

1009

kW

2.07

1.89

1.70

1.54

1.38

1.1

CFM

3321

3114

2906

2681

2455

RPM

1122

1096

1070

1043

1015

kW

2.03

1.84

1.64

1.46

1.27

1.2

CFM

3423

3198

2964

2729

2492

RPM

1162

1132

1103

1074

1046

kW

2.17

1.91

1.56

1.20

1.20

1.3

CFM

3268

3033

2783

2533

RPM

1169

1140

1110

1080

kW

2.12

1.84

1.63

1.41

1.4

CFM

3347

3106

2864

2590

2315

RPM

1203

1174

1145

1115

1085

kW

2.26

2.01

1.75

1.56

1.36

1.5

CFM

3399

3174

2924

2673

RPM

1231

1206

1178

1149

kW

2.37

2.08

1.86

1.63

1.6

CFM

3235

2993

RPM

1236

1210

kW

2.23

1.98

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 10. Blower Performance for P6SP-090* Units

(7.5 Ton Horizontal Models Only)