Installation Instructions

Light Commercial Series Accessory - R-410a Equipment

Low Ambient Kit, Differential Pressure Control

This kit will allow the installation of a differential head-pressure
control on Nordyne, Light Commercial Packaged Gas/Electric
and Electric/Electric units for cooling operation under low
ambient conditions. The differential pressure switch will
monitor the Stage 1 compressor discharge pressure and
cycle the outdoor fans on-and-off in order to protect the
compressor from low suction line conditions.

WARNING:

This kit is to be installed by a qualifi ed service
technician in accordance with these instructions
and all codes having jurisdiction. Failure to follow
these instructions could result in serious injury,
property damage, or death.

WARNING:

All electrical wiring must comply with the latest
edition of the National Electrical Code ANSI/NFPA
70.

These instructions are primarily intended to assist qualifi ed
individuals experienced in the proper installation of this
appliance. Some local codes require licensed installation/
service personnel for this type of equipment.

Kit Contents:
1. Differential Pressure Control for R-410a with integral

capillary tube
a. Pressure

Control

b. Pressure Control Parts bag:

i.

10-32 screws & washers (2 ea.)

c. Manufacture’s Installation Instructions
d. Indoor Mounting Bracket (not used)

2. Outdoor Mounting bracket
3. Outdoor bracket Cover-plate
4. Electrical wires for control connection:

i.

200” – long:

12.5 & 15T models

ii. 90” – long: 6 – 10T models
iii. Jumper wire assembly (orange): 7.5-15T

models

5. Parts

bag:

a. Service

Valve

“T”

fi

tting

b. 7/8” Star bushing
c. 4” long – sheet metal edge guard
d. #10 – ½” Self drilling/tapping screws (2 ea.)
e. # 10 – ½” Blunted screw (1 ea.)
f.

Zip-ties (6 ea.)

g. Warning

Sticker

6. These

Instructions

Installation Instructions
1. Set Indoor thermostat to “Off” position.
2. Disconnect all electrical power to appliance.
3. Remove the stage 1 compressor access panel or grill

and the control panel access panel.

4. Install Low ambient control to the mounting bracket using

the two (2) 10-32 mounting screws & washers that are
located in the box for the pressure control. (See Figure 1.)
Install the 7/8” Star bushing in the bottom of the pressure
control.

Figure 1.

Figure 2.

WARNING LABLE

OUTDOOR CONTROL

COVER

CONTROL ADJUSTMENT

PRESURE CONTROL

PRESURE CONTROL
MOUNTING SCREWS
(#10-32)

OUTDOOR MOUNTING
BRACKET

CONTROL COVER MOUNTING
USE BLUNT-TIP SCREW

5. Install the Low ambient control/mounting bracket assembly

to the Stage one compressor base-plate. Center the
bracket between the compressor mounting bolts and
use the self-tapping screws to attach the bracket to the
base-plate.