Reznor R6GN Option - Installation - Motorized Damper User Manual

Installation instruction

Advertising
background image

INSTALLATION

INSTRUCTION

INSTALLATION INSTRUCTIONS FOR

555633

MOTORIZED (OAD) OUTSIDE AIR DAMPER USED WITH

GR4GM 150/180 UNITS

SUPERSEDES 10-22-04
AUGUST 26, 2008

NEI35MA10

Figure 1

CONTROL MOTOR

WIRE HARNESS

FORM# 655B-0808 (655B-0504)

DAMPER SECTION

MOUNTING HOLES

(STEP 3)

OAD PANEL REMOVED FROM UNIT

OAD SLIDE DAMPERS

Note: 919275 Fresh Air hood is re quired

I - SHIP PING AND PACK ING LIST

Package 1 of 1 contains:

1 - Damper Section with Motor
6 - Screws 10 x ½ x 16 Hex Tex

Check contents for shipping damage. Contact the last carrier
immediately if any shipping damage is found.

II - AP PLI CA TION

The Outside Air Dampers (OAD) are designed to fit the Return
Access Panel. The motorized dampers use a 2-position motor that
opens when blower is energized.

III - IN STAL LA TION

DIS

CON

NECT ALL ELEC

TRI

CAL POWER TO THE UNIT

BE FORE SER VIC ING.

1.

Remove fresh air hood and OAD panel from unit.

2.

Remove OAD slide dampers and set to side for later use.

3.

Align damper section to mounting holes in OAD panel and
secure using screws provided on this kit. See Figure 2.

4.

Replace OAD slide dampers in desired position.

5.

Place OAD Panel back in same place unit panel was located.
Connect (P1) plug from OAD to (S1) economizer plug on unit.

6.

Replace fresh air hood over OAD panel and secure using
screws removed in Step 1. Seal any corners, clearance holes,
etc. to ensure a watertight seal.

7.

Restore all electrical power to the unit.

8.

Check proper operation of the Outside Air Damper by

energizing the indoor blower motor. Ensure wire harness is
secured out of the way and dampers operate when 24V power
is supplied.