Reznor R6GN Option - Installation - Power Exhaust User Manual

Warn ing

Advertising
background image

Fig ure 1

A/C UNIT W/ ECONOMIZER
INSTALLED

POWER EXHAUST

RELIEF HOOD

FAN BLADE

FAN BLADE

IN STAL LA TION

IN STRUC TION

INSTALLATION INSTRUCTIONS FOR

555622 / 555623

POWER EXHAUST USED WITH GR4GM-150/180 (R-22)

and R6GN-150/180 (R410A) UNITS

FORM# 656B-0509 (656B-0604)

CONTROL ACCESS

I - SHIP PING AND PACK ING LIST

Package 1 of 1 contains:

1

- Power Exhaust Assembly

1

- Hardware Bag

11

- #10 -16 x ½" Type A Screws

1

- 1 ¾" Bushing

Check contents for shipping damage. Contact the last carrier
immediately if any shipping damage is found.

II - AP PLI CA TION

Power exhaust can be used in down flow and horizontal
applications. This power exhaust is designed to relieve excess
pressure that may occur with economizers or certain building
conditions. All fan motors are recognized by UL. Permanently
lubricated ball bearing and motor overload protection are standard.

Fig ure 2

III - IN STAL LA TION

1.

Disconnect all power to unit.

2.

Remove the relief hood of economizer, if previously installed, and retain the screws for later use.

Warn ing:

Read these instructions in their entirety before proceeding with the installation of the power exhaust unit, control
components, and its wiring.

This kit is to be installed by a qualified service
technician in accordance with these instructions and
all codes having jurisdiction. Failure to follow these
instructions could result in serious injury, property
damage, or death. These instructions are primarily
intended to assist qualified individuals experienced in
the proper installation of this appliance. Some local
codes require licensed installation/service personnel
for this type of equipment.

Table 1

12.5 and 15 Ton Package Systems - R4GM and R6GN Series

Nordyne

Part No.

Volts

Phase

No. of

Fans

HP

High Speed

FLA

Fuse

MCA

2

MOP

2

CFM

1

RPM

555622

208

3

2

¾

9800

1050

10.00

15

12.50

20

230

555623

460

3

2

¾

9800

1050

5.00

7

6.25

10

Note:
1.

CFM is per fan curve @ 0.1" w.c. ex ter nal static pres sure

2.

Ap pli ca ble to R6GN Mod els

FRESH AIR HOOD

Advertising