Reznor VR Option - Installation - Dual Vent Kit User Manual

Dual vent kit, option cc5, Description/ application

Advertising
background image

Form RZ-NA-I-VR/TRPA-DV, P/N 120733 (Rev 3), Page 1

®

WARNING: Improper installation, adjustment,
alteration, service, or maintenance can cause
property damage, injury or death. Read the
installation, operation, and maintenance
instructions thoroughly before installing or
servicing this equipment.

Dual Vent Kit, Option CC5,

for INFRA-REZ Heater

Models VR, TRPA,

TRP, and TR/TR-H

Installation/Operation Form I-VR/TRPA-DV

Obsoletes Form I-VR/TRP-DV

Description/
Application

The dual vent option kit permits power venting of two of the INFRA-REZ heater

models of tubular radiant heaters through only one opening in the roof or side wall of

a building. The concentric design of the vent allows each of the two heaters to be

safely operated totally independent of the other. The two heaters may be controlled

by the same or different thermostats. Heaters vented through the optional dual vent

do not have to match in capacity, length, configuration or model. The adapter box in

the dual vent kit converts the two separate vent pipe runs into the concentric vent

terminal arrangement. The dual vent adapter box is an aluminized sheetmetal box

that attaches indoors, close to the wall or roof opening.

Kit Components

Vent Length and
Vent Pipe
Requirements

FIGURE 1 -
Option CC5
Dual Vent Kit

WARNING: Installation should be done by a qualified agency in
accordance with these instructions and in compliance with all
codes and requirements of authorities having jurisdiction. The
qualified agency performing this work assumes responsibility for
this installation.

References:

Model VR

- Refer to Heater Installation Form I-VR, Paragraph 13

Model TRPA

- Refer to Heater Installation Form I-TRPA, Paragraph 9

Model TRP

- Refer to Heater Installation Form I-TRP, Paragraph 9

Models TR/TR-H

- Refer to Heater Installation Form I-TR, Paragraph 11

Include the length of the concentric pipe and the equivalent for the flow loss through

the adapter box in the vent length of each heater. See the Vent Length Table, page

2, for maximum allowable vent lengths by model, size, and straight length of tubes.

Maximum length of the concentric portion of vent pipe is six feet (1.8M).
Vent pipe is field-supplied. Use only single-wall metal pipe.

1

2

4 & 5

3

Option CC5, Package P/N 120736, include s:

Code

Qty

P/N

De scription

1

1 120290 Dual Vent Adapter Box

2

1 110051 4" Vent Cap

3

1 120869 6" Vent Cap

4

1

53335 Tube of High Temperature

Silicone

5

2 120108 Support Angles