4.2 Gas Heat Section Controls

4. Gas Heat

Section

Maintenance

(cont'd)

4.2.2 Ignition System (Natural Gas only)

The modulating furnace has the control module in the control compartment (

FIGURES

12 and 13A) with an additional board (FIGURE 13B) attached directly to the side of

the burner to control spark. Do not attempt to disassemble either board. However, each

heating season check the lead wires for insulation deterioration and good connections.
If replacement is required, these boards must be replaced with identical parts.

FIGURE 13A - Ignition Control

Module (Deep Modulation Board)

The control has a built-in, self-diagnostic capability. The control continuously monitors

its own operation and the operation of the heat section including direct spark ignition,

safety and modulating valves, and venter motor speed. The 3-digit display on the con-

trol indicates the current system state, warnings, failures, and test modes.

3-Character Display

ID

Plug

IMPORTANT: The control module illustrated

is

P/N 257246 used on all MAPSIII Cabinet

D heat sections manufactured beginning

8/2011 and on previously manufactured

units as a special. The ID plug on each

board is unique for each size of heat section.

A replacement board will require either a

new ID plug or reuse of the ID plug from the

board being replaced.
Standard MAPSIII Cabinet D heat sections

manufactured prior to 8/2011 have a unique

ignition board by size and do not have a

replaceable ID plug.

Normal Furnace Operation (LED 3-Character Display in FIGURE 13A)

LED Display

Heat Mode

Description

OFF Mode (OFF) System Idle - Control board has power, no faults found, no call for heat.

PURGE Mode

(Pur)

System is purging the heat exchanger – No gas on, no flame, inducer runs for

the specified purge timings. Purge cycles occur immediately before and after

each burner operation.

IGNITION Mode

(Ign)

System is initiating burner operation – Igniter energized, modulating valve

moved to ignition setting, gas on. Maintained for the trial-for-ignition period

and the five second flame stabilization period.

WARM-UP Mode

(HEA)

Period between Ignition and Run – System checks completed before

modulation control begins.

RUN Mode (run)

Normal modulating operation.

Ignition Retry (rEt) System has had a failed ignition attempt or has lost flame during burner

operation and is beginning another ignition cycle.

Controller LED Information (displayed on power up)

Display Info (example only) Description

D CAb

Furnace series or model name, for example, "D cabinet

series"

500

Heat Section Size

nAt

Fuel type

1.01

Software version

NOTE: Operating and

Lockout Error Codes

displayed on ignition

controller 3-character

display (

FIGURE 13A) are

listed in Troubleshooting

Paragraph 7.3.3.

FIGURE 13B - Spark

Ignition (DSI) Board,

P/N 257975

Spark Board is attached

to the side of the burner.

CAUTION: Due to high

voltage on the spark wire

and electrode, do not

touch when energized. See

Hazard Levels, page 2.