Reznor Carryover Lighter Tube Parts Manuals User Manual

Description/application, Installation instructions, Caution: hold burner rack firmly and pull slowly

Advertising
background image

Form RZ-NA-P-X/XE-LTR-TUBE, Mfg #101147, Page 1

Installation Instructions for

Carryover Lighter Tube - Natural or

Propane Connection

Parts/Installation Form RZ-NA-P-X/XE-LTR-TUBE

Obsoletes RGM 704 (Version A)

APPLIES TO:

Model Series X, RX, XE, RXE, REB

Description/Application

These carryover kits are intended for installation on Model (H) (C) RX; (H) (C) X; (H) (C) RXE; (H) (C) REB, and (H) (C) XE that did not include

factory-installed lighter tube carryovers (units manufactured prior to 11/86).

Parts List (Lighter Tube Carryover Kits are listed by Size of Heater)

WARNING: All components of the gas supply system
must be leak tested prior to placing equipment into
service. Never test for leaks with an open flame.
Failure to comply could result in severe personal
injury or death. Use an approved leak-test solution
or soap solution to detect leaks.

Size

75/100

125

150/175 200/225 250/300

350

400

For NATURAL GAS Furnace - Kit P/N

92135

92136

92137

92138

92139

92140

92141

Components:
Lighter Tube Assembly

9899

9859

9821

9783

9747

9711

9520

Length (inches)

12-3/8

15-1/8

20-5/8

26-1/8

34-3/8

39-7/8

45-3/8

Drip Shield

15015

15014

15013

15012

15011

15010

14957

Carryover Orifice

9870

9870

9680

10370

10370

9792

9792

Drill Size

70

70

65

59

59

54

54

Aluminum Tube

93389

93389

93389

93389

93389

93389

93389

Brass Elbow

93388

93388

93388

93388

93388

93388

93388

Compression Fitting

9664

9664

9664

9664

9664

9664

9664

1/2" lg, #10 Sheetmetal Screw

11813

11813

11813

11813

11813

11813

11813

Quantity

6

6

6

6

6

6

6

For PROPANE GAS Furnace - Kit P/N

92142

92143

92144

92145

92146

92147

92148

Components:
Regulated Carryover Assembly

100712

100712

100712

100712

100712

100712

100712

Lighter Tube Assembly

9899

9859

9821

9783

9747

9711

9520

Length (inches)

12-3/8

15-1/8

20-5/8

26-1/8

34-3/8

39-7/8

45-3/8

Drip Shield

15015

15014

15013

15012

15011

15010

14957

Carryover Orifice

9870

9870

9680

9680

10370

9791

9791

Drill Size

70

70

65

65

59

56

56

1/2" lg, #10 Sheetmetal Screw

11813

11813

11813

11813

11813

11813

11813

Quantity

6

6

6

6

6

6

6

Drip

Shield

Lighter
Tube

Regulated
Carryover
Assembly for
Propane Gas

Installation Instructions

1.

Turn off the gas supply upstream of

the valve and turn off the electric.

2.

Mark the wires connected to the gas

valve and disconnect.

3.

Disconnect spark lead and flame sen-

sor from the ignition controller.

CAUTION: Hold burner rack firmly and pull slowly.

4

. Remove the burner rack.

a) Remove the heater side panel.

b) Uncouple the union in the gas supply to

permit removal of the burner rack.

c) Remove the sheetmetal screws in the top

corners of the burner rack and pull the

burner rack out of the unit.

5.

Follow the illustrated instructions on

pages 1-4 to install the Lighter Tube

Carryover Kit. Test for leaks. When the

installation is complete, reverse Instal-

lation Instruction Nos. 1-4 to re-

assemble the heater. Test for proper
and safe operation.

INSTALL LIGHTER TUBE - Steps 1-6 apply both natural gas and propane gas heaters.

1. Burner rack

without
lighter tube.

2. Back off screws that

attach the manifold
to the burner rack.
Remove top screws.

®

Advertising