5220 Direct Connect Module

Installation Instructions

The 5220 is a direct connect module used to
connect a fire alarm control panel (FACP) to a
city box or polarity reversal communicator. The
following instruction are generic installation
instructions, refer to the FACP installation
manual for compatibility and usage.

Note: Installation and wiring of this device must be done in

accordance with NFPA 72 and local ordinances.

Specifications

Mounting

The 5220 comes equipped with its own cabinet
assembly. The 5220 is intended for indoor use
only in a dry location.
1. Remove the cover from the 5220.
2. Mount the 5220 with four screws in the holes

shown in Figure 1.

Figure 1: Mounting the 5220

3. Wiring the 5220 as shown in Figure 2.
4. Replace the 5220 cover and secure it with

the two self-tapping screws supplied.

Operating Voltage: 19.4 to 28 VDC
City Box Current : 1 A for 1 Second,
max coil resistance 30 ohms
Polarity Reversal: 20 mA max.,
max loop resistance 3 k ohms
Ambient Temperature: 32°F to 120°F (0°C to 49°C), or
humidity within the range of 10%-93% at 30°C (86°F)
noncondensing.
Dimensions: 6-1/2”W x 1-5/16”H x 2-1/8”D
(16.51 cm W x 3.33 cm H x 5.40 cm D)
Terminal Wire Rating: 12 - 24 AWG

Mounting Holes

Mounting Holes

Cover Screw

Hole

Cover Screw
Hole