SilentKnight 5280 Status Display Module for 5208 User Manual

Mounting the 5280

Advertising
background image

P/N 151238

SK-5280 Status Display

Module Installation

Instructions

The following instructions are a quick reference guide, refer to
the control panel installation manual for detailed system
information.
The SK-5280 Status Display module provides outputs and
control functions for remote annunciation of alarm, trouble, and
supervisories for each zone.
Note:

The driver outputs are non-supervised.

Figure 1: Model 5280 Board Layout

The SK-5280 has 1 connector which has 10 outputs for alarms
and 10 outputs for trouble annunciation. These outputs are active
low. Each output can provide up to 100 mA of current, with a
total limitation of 700 mA. The module has 4 normally open non-
dedicated relays that can be wired to be active with any of the
outputs. The system can supervise up to 8 5280 Status Display
Modules.
Wire the SK-5280 as shown in Figure 2. Maintain a physical
separation of one-half inch or more between field wires and
connection points to prevent damage from transients.
Note: SILENCE does not affect SK-5280 outputs. To reset a SK-

5280 output, the alarm or trouble condition must be
restored.

The SK-5280 can be used to interface to LED annunciator.
The SK-5280 can be programmed to indicate alarms and trouble
status for; zones 1 - 10, zones 11 - 20, zones 21 - 30, or system
status outputs.

Figure 2: SK-5280 Connection to the Control Panel

Mounting the 5280

The SK-5280 mounts onto a metal bracket and standoffs in the
SK-5208 cabinet or into SK-2190 accessory cabinet.

Mounting the SK-5280 into

SK-5208 Cabinet

Follow these steps to properly mount the SK-5280 into the
SK-5208 cabinet:
1.

Remove power from the control panel.

2.

Mount the SK-5280 onto the standoffs and bracket located
in the cabinet. See Figure 3.

Figure 3: Installing the 5280 Into the 5208 Cabinet

3.

Connect the SK-5280 to the SK-5208 control panel as
shown in Figure 2.

4.

Set the ID number. See the 5208 Installation Manual (PN
151204) for information on setting ID numbers.

5.

Reconnect power to the control panel.

Trouble Outputs

ID Number
DIP Switch

SBUS Connector

4 On-board Relays

Regulated Alarm

Outputs

1/4” spacing must be maintained between

all power limited & non-power limited wiring

Relays are non-power

limited

SBUS is power limited

Control
Panel

5280

Supervised
Power Limited