Model 5495 Distributed Power Module Installation Manual

20

151161

4.8.2

Selecting Synchronized Output Configurations

The following sections describe how to configure the 5495 as a synchronization
power expander for Amseco, Faraday, Gentex, System Sensor, or Wheelock
synchronized horn/strobe appliances.

Note: In order for the synchronization feature to operate properly, make sure you have set the DIP

switches for the proper manufacturer. See Sections 4.8.2.1, 4.8.2.2, or 4.8.2.3.

4.8.2.1 Selecting Synchronized Faraday Configurations

To select the input/outputs for Faraday synchronized appliances, set the DIP
switches as shown in Figure 4-9.

Figure 4-9 Faraday Synchronized Configurations

4.8.2.2 Selecting Synchronized Gentex Configurations

To select the input/outputs for Gentex synchronized appliances, set the DIP switches
as shown in Figure 4-10.

Figure 4-10 Gentex Synchronized Configurations

Important!

For all synchronization options, input 1 is the strobe input and input 2 is the audible input. The signals to input 1
and input 2 must be DC signals for the synchronization patterns to work properly. When it is desired to activate
both strobes and audibles, input 1 and input 2 must be active. If it is desired to only activate strobes, then input 1
must be active and input 2 must be inactive. The audible can be deactivated and reactivated at any time by
changing the signal at input 2 as long as input 1 remains active. If input 1 is not active, then input 2 is ignored.