SilentKnight 5880 LED Driver Module User Manual

5880 led i/o module installation instructions, Specifications mounting the 5880 enclosure, Wiring the 5880 to the facp

Advertising
background image

P/N 150972

5880 LED I/O Module

Installation Instructions

The 5880 provides a way to customize your
remote annunciator when used with a
compatible addressable fire alarm control panel
(FACP). For more detailed information, refer to
the FACP installation manual.

Note: Installation and wiring of this device must be done in

accordance with NFPA 72 and local ordinances.

Specifications

Mounting the 5880

Enclosure

The 5880 comes in a plastic enclosure which
must be mounted inside the annunciator or
accessory cabinet.
To mount the 5880 plastic enclosure into the
appropriate cabinet:
1. Remove the 5880 cover. Use a small screw

driver if necessary.

2. Remove the 5880 circuit board from the base

by pushing outward on the base snap
retaining tabs and lifting the circuit board
out.

Figure 1: 5880 Circuit Board And Plastic Base

3. Mount the plastic base into the appropriate

accessory cabinet.

4. Replace the circuit board in the plastic base.

Note: It may be necessary to connect the wiring to the circuit

board before the board is replaced into the base.

Wiring the 5880 to the FACP

Terminate the wiring as shown in Figure 2 and
Table 2.

Figure 2: 5880 Connection to the FACP

Table 1: 5880 Specifications

Max. SBUS Voltage

24 VDC

Dry Contacts
(Loop Specs)

Max. Loop Resis-
tance

100

Ω

Max. Loop Voltage

24 VDC

Max. Loop Current

2 mA

Max. Current

Alarm

200 mA

Standby

35 mA

Each LED

10 mA

Open Collector PZT Max. Sink Current

100 mA

Operating Temperature

0° to 49° C
(32° to 120° F)

Max Wiring Distance from FACP

6,000 ft
(1,829 m)

Indoor Use Only

Snap

Base

Circuit

Board

Retaining Tabs

FACP

Supervised

Power Limited

5880

Advertising