SilentKnight B200SR-LF Low Frequency Intelligent Sounder Base User Manual

B200sr-lf low frequency intelligent sounder base

Advertising
background image

SS-450-013

1 I56-4152-002R

B200SR-LF
Low Frequency Intelligent Sounder Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEFORE INSTALLING
Please read the System Sensor Smoke Detector Application Guide, which pro-
vides detailed information on sensor spacing, placement, zoning, wiring, and
special applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed. The National Fire Alarm
Code, NFPA 72, requires effective January 1, 2014, that audible appliances
installed in sleeping areas produce a low frequency alarm signal that shall be
a square wave or provide equivalent awakening ability with a fundamental
frequency of 520 Hz +/– 10%.
NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at
least once a year.
GENERAL DESCRIPTION
The B200SR-LF low frequency sounder base is used with System Sensor 200-Se-
ries sensor heads or equivalent. For a list of compatible sensors, refer to the Sys-
tem Sensor website at www.systemsensor.com. Refer to the appropriate manual
for more information on sensors.

The B200SR-LF low frequency sounder base generates a low frequency tone
around 520 Hz. Studies have shown that low frequency audible devices that
operate around 520 Hz are more effective in waking individuals in sleeping
areas. It offers maximum flexibility in configuration and operation to meet or
exceed the requirements of UL268 and UL464.

The sounder base is capable of producing either the distinctive three-pulse
temporal pattern (ANSI Temporal 3) fire alarm signal now required by NFPA
72 for commercial and residential applications or a continuous tone by simply
removing the included jumper from the device. Additionally, the B200SR-LF
is designed to be compatible with existing installations of B501-Series sounder
bases.

The sounder base is intended for use with intelligent systems. The sounder
base requires an external 24 VDC power supply. The connections for the
external power supply and the communication loop are isolated to prevent
electrical interaction between them. Refer to the panel manual for maximum
allowable number of units per loop.
NOTE: For NFPA72 Installations, the Temporal 3 tone should be used for public
mode evacuation.
NOTE: When not used as a supplementary evacuation system, the external 24
VDC supply shall be treated as a component of the main power supply system
and shall fall under the requirements of the main power supply system per
NFPA 72.

SPECIFICATIONS
Base Diameter:

6.875” (17.46 cm)

Base Height (less sensor):

2.0” (5.08 cm)

Weight:

0.6 lb. (272 gm)

Operating Temperature Range:

Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com

Operating Humidity Range:

10% to 93% relative humidity (non-condensing)

External Supply Electrical Ratings
External Supply Voltage:

16 to 33 VDC (VFWR)

Standby Current:

1mA maximum VDC

Alarm Current:

65 mA maximum @ 33.0 VDC

90 mA maximum @ 24.0 VDC

125 mA maximum @16.0 VDC

SLC Electrical Ratings
SLC Operating Voltage:

15 to 32 VDC

SLC Standby Current:

Refer to applicable sensor specification

Sound Output

Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)

WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction and must not be of such length or wire
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and
accessory devices should be color coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from responding properly
in the event of a fire.

Wire sizes up to 12 AWG (2.5 mm

2

) may be used with the base. The sounder

base will be shipped with the screw terminals set for 14 AWG wiring. If 12
AWG wire is to be used, back out the screws to allow the wire to fit beneath
the clamping plates. For best system performance, the power (+ and -) wires
and the communication circuit wires should be twisted pair or shielded cable
installed in a separate grounded conduit to protect the communication loop
from electrical interference.

Make wire connections by stripping about 3/8” of insulation from the end of
the wire. Then, slide the bare end of the wire under the appropriate clamping
plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the
wire under the clamping plate (See Figure 2) The wiring diagram for a typical
2-wire intelligent system is shown in Figure 4.

CAUTION

For system monitoring - for terminals 4 and 5, do not use looped wire under termi-
nals. Break wire run as shown in Figure 2 to provide monitoring of connections.

B200SR-LF TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Sounder Base Interconnect

I56-4

152-00

2R

Advertising