SilentKnight HFS-MM User Manual

Hfs-mm miniature monitor module, Installation and maintenance instructions

Advertising
background image

Mounting and Wiring
NOTE: This module is intended to be wired and mounted without rigid con-
nections inside a standard electrical box. All wiring must conform to appli-
cable local codes, ordinances and regulations.

1. Connect the red (+) and black (–) wires to the positive and negative loop

power leads of the signaling line circuit (SLC).

2. Connect the violet (+) and yellow (–) wires to a two-wire, normally open

initiating loop.

3. Install the specified EOL resistor value to terminate the initiating loop.
4. Reference the control panel device address map to determine appropriate

addressing.

5. Set the address on the module per job drawings.
6. Install the module in the desired mounting location.
Figure 2. typical 2-Wire style B initiating device circuit
conFiguration:

0

7

8

6

5

4

3

2

1

9

10

11

12

13

1415

(+)

(–)

TO

NEXT

DEVICE

BLACK

RED

(+) (–)

(+)(–)

VIOLET

YELLOW

0 1

2

3

4

5

6

7

8

9

SIGNAL LINE CIRCUIT (SLC)

47k EOL

INCLUDED

(ELR-47k)

UL LISTED

COMPATIBLE

CONTROL

PANEL

ALL WIRING

SHOWN IS

SUPERVISED AND

POWER LIMITED

TENS

ONES

C0614-02

HFs-MM Miniature Monitor Module

HW-460-016

1

I56-3487-000

©2009 Honeywell International, Inc.

BeFore installing
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
general description
The HFS-MM minitature monitor module can be installed in a single gang
junction box directly behind the monitored unit. Its small size and light weight
allow it to be installed without rigid mounting (see Figure 1). The HFS-MM is
intended for use in intelligent, two-wire systems where the individual address
of each module is selected using rotary switches. It provides a two-wire initiat-
ing device circuit for normally open contact fire alarm and security devices.
coMpatiBility requireMents
To ensure proper operation, this module shall be connected to listed-compat-
ible control panels only.
Figure 1:

C1063-00

speciFications
Nominal Operating Voltage:

15-32 VDC

Average Operating Current:

375µA maximum (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)

EOL resistance:

47K Ohms

Maximum SLC Wiring Resistance:

40 Ohms

Maximum IDC Wiring Resistance:

1,500 Ohms

Maximum IDC Voltage:

11 Volts

Maximum IDC Current:

450µA

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10% to 93% Non-condensing

Dimensions:

1.3˝ H x 2.75˝ W x 0.5˝ D

Wire Length:

6˝ minimum

I56-3487-000

installation and Maintenance instructions

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

R E V I S E D

by the Graphic Development Department

Please review all content carefully.

11:45 am, Aug 07, 2009