GeneRaL DeSCRIPtIOn
Models HFS-P and HFS-PT are plug-in type smoke sensors with a plug-in de-
tector base that combine a photoelectronic sensing chamber with address-
able-analog communications. The sensors transmit an analog representation
of smoke density over a communication line to a control panel. Rotary de-
cade switches are provided for setting the sensor’s address. The detector is
intended for use in a 2-wire intelligent system, with screw terminals provided
for power (+ and –).

Two LEDs on the sensor are controlled by the panel to indicate sensor sta-
tus. Model HFS-PT combines a photoelectronic sensing chamber and 135°F
(57.2°C) fixed temperature heat detector.

The HFS-P and HFS-PT require compatible addressable communications to func-
tion properly. Connect these sensors to listed-compatible control panels only.

Communication takes place over the power (+ and –) lines.
BaSe teRmInaLS (See FIGURe 1)
NO. FUNCTION
1 Power (–)
2 Power (+)
SPaCInG
Space sensors in compliance with NFPA 72. In low air flow applications with
smooth ceilings, space sensors 30 feet apart. For specific information regard-
ing sensor spacing, placement, and special applications, refer to NFPA 72 or
the System Smoke Detector Application Guide.

NOTE: These products are not listed for use inside duct smoke detectors.
mOUntInG
This detector base mounts directly to 3½- and 4-inch octagon boxes, 4-inch
square boxes (with or without plaster rings, see Figure 2), and single gang
boxes. Install the base on the box using the screws supplied with the junction
box and the appropriate mounting slots in the base.
WIRInG GUIDe
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Hav-
ing Jurisdiction. Proper wire gauges should be used. The conductors used to
connect smoke detectors to control panels and accessory devices should be
color-coded to reduce the likelihood of wiring errors. Improper connections
will prevent a system from responding properly in the event of a fire.

For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring or shielded cable for the power (+ and –) loop is
recommended to minimize the effects of electrical interference.

HFS-P and HFS-Pt
Intelligent Photoelectric Smoke Sensors
with Plug-In Detector Base

I56-3483-000R

InStaLLatIOn anD maIntenanCe InStRUCtIOnS

SPeCIFICatIOnS
Operating Voltage Range:

15 to 32 VDC

Standby Current:

300µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

Maximum Alarm Current (LED on):

6.5 mA @ 24 VDC

Operating Humidity Range:

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range:

32°F to 120°F (0°C to 49°C), HFS-P; 32°F to 100°F (0°C to 38°C), HFS-PT

Air Velocity:

0 to 4000 ft/min

Height:

2.0˝ (51 mm)

Diameter:

6.1˝ (155 mm)

Weight:

5.7 oz. (162 g)

Mounting:

4˝ (102 mm) square box with or without plaster ring; Minimum Depth – 1½˝ (38 mm)

4˝ Octagon Box; Minimum Depth – 1½˝ (38 mm)

3½˝ Octagon Box; Minimum Depth – 1½˝ (38 mm)

Single Gang Box; Minimum Depth – 1½˝ (38 mm)

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

FIGURe 1. teRmInaL LayOUt:

FIGURe 2. mOUntInG DeteCtOR tO BOx:

BASE

TERMINALS

1

2

C0127-01

C0128-02

SCREWS

(NOT SUPPLIED)

DETECTOR

BASE

BOX

(NOT SUPPLIED)