SilentKnight PS-DASP Pull Station User Manual

Ps-sa manual pull station

Advertising
background image

PS-SA Manual Pull Station

Patented, U.S. Patent No. Des. 428,351; 6,380,846

Document 51412-2

I56-2830-001

Description

The PS-SA pull station is a non-coded, single-action manual pull station with pigtail con-

nections and a key-lock reset feature. It provides Silent Knight control panels with one

normally open (N/O) alarm initiating input. The PS-SA meets the ADAAG controls and

operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5 lb.

maximum pull force to activate the pull station. Operating instructions are molded into the

pull station handle along with Braille text.

Ratings

Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or DC).

Installation

The PS-SA pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or

semi-flush mounted on a standard single-gang, double-gang or 4˝ (10.16 cm) square electrical

box. The optional BG-TR trim ring can be used if the PS-SA is to be semi-flush mounted.

Operation

To activate the single-action pull station, simply pull down the handle. The word ‘ACTI-

VATED’ appears after the handle is pulled down. This will remain until the pull station is reset.

The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)

switch which closes upon activation of the pull station.

Resetting the Pull Station

1. Insert the key into the lock and rotate

1

/

4

-turn counterclockwise.

2. Open the door until the handle returns to normal.

3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Opening

the door will not activate or deactivate the alarm switch.

P0252-00

RED

‘PIGTAILS’

BLACK IN/OUT (–)

RED IN/OUT (+)

BLACK

P0209-01

Wiring

CAUTION!

Do not detach the door of the pull station during installation. The door of the pull station

cannot be reattached to the backplate after the backplate has already been installed onto an

electrical box.

CAUTION!

Install the Silent Knight PS-SA pull station in accordance with these instructions,

applicable NFPA standards, national and local Fire and Electrical codes and the requirements

of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conduct-

ed in accordance with the appropriate NFPA standards. Failure to follow these directions may

result in failure of the device to report an alarm condition. Silent Knight is not responsible for

devices that have been improperly installed, tested or maintained.

ADA Compliance

For ADA compliance, if the clear floor

space only allows forward approach to an

object, the maximum forward reach height

allowed is 48 inches (121.92 cm). If the

clear floor space allows parallel approach

by a person in a wheelchair, the maximum

side reach allowed is 54 inches (137.16 cm).

PS-SA

Manual Pull Station

12 Clintonville Road

Northford, CT 06472

203-484-7161

Fax: 203-484-7118

www.silentknight.com

©2009 Honeywell International Inc.

06/09

Document 51412-2

I56-2830-001