SilentKnight SD500-ANM Addressable Notification Module User Manual

Sd500-anm installation instructions, Wiring the sd500-anm, Sd500-anm specification

Advertising
background image

P/N 151109

SD500-ANM
Installation Instructions

The following instructions are a quick reference
guide, refer to the control panel installation
manual for detailed system information.
The SD500-ANM (Addressable Notification
Module) is an output accessory module for the
IntelliKnight Fire Control Panel, which provides
one reverse polarity supervised notification
appliance circuit. The notification circuit can be
configured in either Class A (Style Z) or Class B
(Style Y).

SD500-ANM Specification

Table 1 list the electrical, physical and
environmental specifications of the SD500-
ANM.

Note: When calculating total alarm current, add the

current ratings of all the notification devices on the
notification circuit.

Wiring the SD500-ANM

Note: Installation and wiring of this device must be done

in accordance with NFPA 72 and local ordinances.

Important!: All wiring is supervised and power limited.

Connecting SD500-ANM to the SLC

The SD500-ANM connection for the SLC loop
internal and external are the same. Wire as
shown in Figure 1.

Figure 1: SD500-ANM Connections to the 5815XL

Table 1: SD500-ANM Specs

Specification Parameter

Rating

Operating Temperature:

32° - 120° F
(0° - 49° C)

Dimensions:

Length:

4-7/8”

Width:

4-7/8”

Depth:

7/8”

Operating Voltage:

24 VDC

Notification Appliance Current:

2 A max.

Notification Outputs

24 VDC
Full Wave Rectified

SLC Current:

.55 mA

Max. SLC Loop Resistance:

50

Ω

Max Impedance Output

1.5

Ω

For indoor use only