SilentKnight SD500-ARM Addressable Relay Module User Manual

5820 board assembly, Silent knight, By honeywell

Advertising
background image

SC-
33

S+
34

SC-
35

S+
36

5820 Board
Assembly

SLC Out

SLC In

N

C

2

-S

LC

+

N

C

1

C

1

N

O

2

C

2

N

O

1

1

2

3

4

5

6

7

8

ON

Relay 1

Relay 2

Figure 1: Typical Wiring

Contacts are Form C,
non-supervised.
Power limited sources only.
Programmable relays.

This sheet is intended to be used for quick reference only. For complete information on wiring, addressing, and
programming this device, refer to the control panel installation manual.

P/N 151091 Rev D

If power-limited circuits are installed
(using types FPL, FPLR, FPLP or
other permitted substitute cables),
they must be separated from all
other conductors by a minimum of
0.25 in. or by a nonconductive
sleeve or barrier.

Model SD500-ARM Relay Module Installation Quick Reference

N

C

2

-S

LC

+

N

C

1

C

1

N

O

2

C

2

N

O

1

Fit screws through notches
on mounting plate. Tighten
screws to secure to box.

Figure 2: Typical Mounting

4-square electrical box

SD500-ARM circuit board

and mounting plate

(assembled at the factory)

Cover plate

4

5

6

7

8

When attaching cover plate,
line up screw holes as shown.

Dipswitch

For device addressing.

See manual for list of

valid addresses.

LED

LED flashes green when

contacts are in normal state;

flashes red when

contacts are activated.

Supervised
Power limited

SILENT
KNIGHT

®

by Honeywell

30 VDC @ 2.0A Resistive
30 VDC @ 1.0 A Inductive (.6PF)
30 VDC @ 0.6 A (0.35PF) Pilot Duty
120 VAC @ 0.6 A (0.35PF) Pilot Duty

Operating Temperature

Operating Voltage

SLC Current

SLC Loop Resistance

Relay Ratings

For indoor use only

32° – 120°F (0° – 49°C)

24 VDC

0.55 mA

50W

Electrical & Environmental Specifications