SD500-PS/SD500-PSDA

Addressable Fire Pull Station

Installation Instruction

The SD500-PS/PSDA is an addressable fire pull
station. The SD500-PS/PSDA is a normally
open initiating point compatible with Silent
Knight Addressable control panels. The SD500-
PS/PSDA is designed for indoor use in non-
explosive environments. Used to activate a non-
coded alarm instantly.
An on-board status LED is visible from the front
of the pull station. The LED flashes to indicate
proper communication with the FACP
(approximately every 30 seconds).

Specifications

Operation

To activate the fire pull station:
1. Grab the top of the pull station where it is

labeled “PULL”.

2. Pull the cover plate out and down.
To reset the pull station:
1. Insert key into the lock.
2. Turn the key clockwise.
3. Close the cover plate.
4. Turn the key counter clockwise.

Wiring to the SD500-PS/PSDA

Wire the SD500-PS as shown in Figure 1.

Figure 1: Fire Pull Station Wiring

Mounting the SD500-PS/PSDA

The pull station mounts to a standard single gang
electrical switch box or a surface mount back
box P/N PS-SMBB (sold separately). See Figure
2.

Parameter

Rating

Max. Line resistance

50

Ω

Max. Alarm
Current

One device in
alarm 23mA. 46
mA for two
devices in alarm.

.5 mA for each
additional device in
alarm.

Max. Voltage

33 V

Operating Temperature

0° to 49° C
(32° to 120° F)

Dimensions

5-1/8” H x 3-1/16” W x 1.5” D

Supervised
Power Limited