SilentKnight SD500-SDM Smoke Detector Module User Manual

Sd500-sdm installation instructions, Specifications compatibility, Wiring

Advertising
background image

P/N 151193

I5

6-3

546-00

0

SD500-SDM Installation
Instructions

The SD500-SDM two-wire smoke module
allows you to connect a loop of conventional
detectors to a Silent Knight addressable fire
alarm control panel (FACP). Each loop can then
be assigned an address on the FACP.

Specifications

Compatibility

The SD500-SDM is compatible with all Silent
Knight addressable FACPs.

Wiring

Note: Installation and wiring of this device must be done in

accordance with NFPA 72 and local ordinances.

Important! All wiring is supervised and power limited.

Connecting the SD500-SDM
to the SLC Loop

The SD500-SDM connections to the 5815XL
internal and external are the same. Wire as
shown in Figure 1.

Figure 1: SLC Wiring

Smoke Detector Connections

This section contain instructions on how to
connect a 2-wire conventional smoke detector
loop to the SD500-SDM for either Class B (Style
B), or Class A (Style D).

Class B (Style B) Wiring

Wire Class B (Style B) conventional smoke
detector loop to the SD500-SDM as shown in
Figure 2. Place the jumper block in the Class B

Specification Parameter

Rating

2-Wire Smoke Detector
Loop Current:

Standby:

2 mA max.

Alarm:

100 mA max.

Operating Voltage:

SLC

32 VDC

Aux Power

24 VDC

SLC Current for battery
calculation:

Alarm:

.55 mA

Standby:

.55 mA

Operating Temperature:

32° - 120° F
(0° - 49° C)

Humidity:

10-85% RH

Max. SLC Loop Resistance:

50

Ω

Max. 2-wire Conventional Smoke Loop
Resistance

50

Ω

Dimensions:

Length:

4-7/8”

Width:

4-7/8”

Depth:

7/8”

For indoor use only