SilentKnight SD505-6IB 6 Isolator Base User Manual

Silent knight, Class a (style 7) configuration, Class b (style 4) configuration

Advertising
background image

P/N 151175

SILENT

KNIGHT

®

SD505-6IB (6” Isolator Base)
Installation Instructions

The SD505-6IB is a 6 inch isolator base that fits
underneath the 6 inch detector base.

Class A (Style 7) Configuration

An isolator base is used to isolate a short circuit
wiring fault on a Class A (Style 7) SLC loop.
Normally if the control panel detects a short on
the SLC loop the entire loop is disabled. When
isolator modules are used (as shown in Figure 1)
and a short, open or ground fault occurs on the
SLC loop, it will be detected as a trouble but all
the SLC devices will continue to operate.

Figure 1: Class A (Style 7) Example

Class B (Style 4) Configuration

Figure 2: Class B (Style 4) Example

1. If a short occurs at point A (Figure 2),

isolator base 1 will activate, isolating SLC
devices 2 and 3 from the rest of the loop.

2. If a short occurs at point B (Figure 2),

isolator base 2 will activate, isolating SLC
devices 5 and 6 from the rest of the loop.

3. If a short occurs at point C (Figure 2),

isolator base 3 will activate, isolating SLC
devices 8 and 9 from the rest of the loop.

SD505-6IB Specifications

Specification Parameter

Rating

Operating Temperature:

32° - 120° F
(0° - 49° C)

Dimensions:

Length:

4-7/8”

Width

4-7/8”

Depth:

7/8”

Operating Voltage:

32 VDC

Battery Current Draw dur-
ing AC loss:

Alarm/Standby:

92 uA

SLC Current:

50 uA

Max. SLC Loop Resistance:

50

For indoor use only

0-50 devices,
up to 10

per

branch

Advertising