SilentKnight SD505-6RB 6 Relay Base User Manual

Silent knight, Wiring

Advertising
background image

P/N 151192

SILENT

KNIGHT

®

SD505-6RB (6

Relay Base)

Installation Instructions

This sheet is intended to be used to install the
SD505-6RB to a Silent Knight Addressable
control panel. Refer to the control panel
installation manual for programming
instructions (P/N 151139 or 151209).

The SD505-6RB adds a relay output function to
a Silent Knight addressable detector. The Form
C relay is rated at 8.0 amps for 240 VAC, 120
VAC and 30 VDC applications.

Specifications

Wiring

This section contains information on how to
wire the SD505-6RB to the SLC Loop of the
control panel, how to wire the SD505-6RB to the
6” detector base, and wiring guide lines for each.

Figure 1 illustrates how to run the wiring for the
SLC loop and relay through the extension base,
and how wiring harness 140675 connects to the
6” detector base.

Note: Low and high voltage wiring must be run through

separate openings on the extension base. See
Figure 1. If you are connecting both power limited
and non-power limited sources to the relay base,
you must use one of the following types of wire,
FPLP, FPLR, or FPL within the box in accordance
to NEC 760.54.

Figure 1: Wiring Parameters

SLC Wiring

The SD505-6RB can be configured for either
Class A (Style 6) or Class B (Style 4)
supervision.

Class A (Style 6)

Figure 2 illustrates how to wire the SD505-6RB
to the SLC loop connectors for Class A (Style 6)
supervision.

Figure 2: Class A (Style 6) SLC Wiring

Parameter

Rating

Relay Contact Rating:

8.0 A @ 30 VDC

8.0 A @ 240/120 VAC

SLC Operating Voltage:

32 VDC

SLC Current for Battery
Calculation:

.082 mA (Alarm and
Standby)

Operating Temperature:

32° - 120° F (0° - 49° C)

Humidity:

10-85% RH

Max. SLC Loop Resistance:

50

Supervised
Power Limited