SilentKnight SD505-6SB 6 Sounder Base User Manual

Wiring, Specifications, Slc wiring

Advertising
background image

P/N 151191

SD505-6SB 6” Sounder Base
Installation Instructions

This sheet is intended to be used to install the
SD505-6SB to a Silent Knight Addressable
control panel. Refer to the control panel
installation manual for programming
instructions (P/N 151139 or 151209).

The SD505-6SB adds an audible output function
to a Silent Knight addressable detector.

Specifications

Wiring

This section contains instructions to wire the
SD505-6SB to the FACP, and auxiliary power.
For system supervision of terminals, do not use
looped wire under the terminals. Break the wire
run to provide supervision of connections. See
Figure 3.

SLC Wiring

The SD505-6SB can be connected to the FACP
for either Class B (Style 4) or Class A (Style 6)
supervision. Connect the SD505-6SB to the
FACP as shown in Figure 1 or Figure 2.

Figure 1: Class B (Style 4) Wiring

Figure 2: Class A (Style 6) Wiring

Figure 3: Correct wiring methods

Parameter

Rating

Operating Voltage:

SLC Loop 32 VDC

Aux. Input 24 VDC

Aux. Input Power
Current:

Standby:

1 mA

Alarm:

34.3 mA

SLC Current Draw for
Battery Calculation:

Standby:

.082 mA

Alarm:

.082 mA

Operating Temperature:

32° - 120° F
(0° - 49° C)

Humidity:

10-85% RH

Max. SLC Loop Resistance:

50

Ω