SilentKnight SD505-ADHR Addressable Duct Housing w/Relay User Manual

Sd505-adhr installation, Specifications mounting instructions

Advertising
background image

P/N 151126

SD505-ADHR Duct Detector Housing

With Relay Module & SD505-DTS

Installation Instructions

The following are instructions on how to install
the SD505-ADHR & SD505-DTS to a Silent
Knight Addressable control panel.

SD505-ADHR Installation

The SD505-ADHR is a duct detector housing
with a built-in relay module that is used to
control a fan motor to stop air flow in a fire
alarm situation.

Specifications

Mounting Instructions

Follow these steps to mount the SD505-ADHR:
1. Remove paper backing from mounting

template (packaged in installation kit) and
affix to duct at installation location.

2. Using the template as a guide, drill the four

mounting holes (3/32” diameter) for duct
detector mounting screws provided (4 # 12 x
1/2” sheet metal screws).

3. Use template as guide to drill or punch holes

for the sampling tubes in the air ducts (1-
3/8” diameter).

4. Clean all holes.
Sampling Tube Assembly
The sampling tubes can be ordered in standard
lengths and cut per requirements. See chart
below for available standard sizes. The intake
sampling tube is a piece of steel piping with a
series of holes drilled the entire length of the
tube. The tube should be cut to a size that allows
it to extend the entire width of the duct.
The holes must be facing into the air flow (see
Figure 1). The exhaust tube is a piece of steel
piping measuring 7 inches.

Specification Parameter

Rating

Alarm Relay Contact Rating:

10 A @ 120/240 VAC

Trouble Relay Contact Rat-
ing:

2.5 A @ 30VDC

Operating Volt-
age:

SLC
Loop:

32 VDC

Aux. Pwr.
Input:

120/240 VAC, 24 VDC/VAC

Aux. Input Power
Current:

24 VDC Standby:

35 mA

Alarm:

75 mA

24 VAC

Standby:

50 mA

Alarm:

90 mA

120 VAC Standby:

10 mA

Alarm:

20 mA

240 VAC Standby:

5 mA

Alarm:

10 mA

SLC Current for
Battery Calcula-
tions

Alarm:

.018 mA

Standby:

.018 mA

Max. SLC Loop Resistance:

50

Ω

Operating Temperature:

32° to 120° F (0° to 49° C)

Humidity:

10-85% RH
SD505-APS

SD505-AIS

Air Velocity:

500-4000 fpm 300-4000

fpm

Sensitivity:

0.85 to 1.15%
per foot

0.5 to 0.81%
per foot