SilentKnight SD505-TCHB100 Handheld Detector Programmer User Manual

Tch-b100-ns programmer operating instructions

Advertising
background image

GENERAL DESCRIPTION:

Remote Programming Cable

(All Modules except DCP-FRCME-S)

Remote Programming Cable

(DCP-FRCME-S)

Programming Buttons

Display

TCH-B100-NS PROGRAMMER OPERATING INSTRUCTIONS

PROGRAMMING BUTTONS

ADDRESS SETTING:

To Remote

Programming Jack

NOTE: PRIOR TO PROGRAMMING ENSURE BATTERY IS CONNECTED.

Remote Programming

Jack

Power on. Automatically reads the address of a sensor. Subsequent

operations will advance the device address by ten.

Power off. Advances the device address by one.

Stores the displayed addresss to the device and is used to read sensor

analog levels.

Analog Photoelectric Smoke Sensor

Analog Ionization Smoke Sensor

Analog Heat Sensor

DCP Fast Response Contact Module

DCP Fast Response Contact Monitor

DCP Signal Output Module

DCP Dual Relay Module

TCH-B100-NS is designed for use with the following products:
ALG-V/ALG-EA

AIE-EA

ATG-EA

FRCME-S

FRCME-4

SOM

R2M

CZM

1.

2.

3.

4.

Install sensor onto programmer, ensuring that sensor protrusions align with programmer grooves.
Press the left gray button to switch programmed on. A battery check message will appear followed by

the devices address ( un-programmed sensors will read address 127).

Set the required address by incrementing the left and right gray buttons (the display will show three red

flashing dots if the address being programmed is different from the device's current address).

When the desired address is present press the red button to store that address. The three red dots on

the display will no longer be present.

LEFT GRAY BUTTON

RIGHT GRAY BUTTON

RED BUTTON

DCP Conventional Zone Module

DWG # HA-06-082

Page 1 of 2, 05-03

PART # 1700-09906

HOCHIKI AMERICA CORPORATION

7051 Village Drive, Suite 100

Buena Park, CA 90621-2268.

DCP Dual Input Monitor Module

DIMM