SilentKnight SK-Control Addressable Notification Module User Manual

Sk-control supervised control module

Advertising
background image

SK-460-005

1

I56-3436-001

SK-Control Supervised Control Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEfORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
SK-Control Supervised Control Modules are intended for use in intelligent,
two-wire systems, where the individual address of each module is selected
using the built-in rotary switches. This module is used to switch an external
power supply to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN, or
SHORT CIRCUIT. The SK-Control has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panels only (list available from Silent Knight).
MOUNTINg
The SK-Control mounts directly to 4-inch square electrical boxes (see Figure
2A). The box must have a minimum depth of 2

1

/

8

inches. Surface mounted

electrical boxes (SMB500) are available.
WIRINg
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. When using control modules in nonpower limited applications,
UL requirements for the separation of power-limited and nonpower-limited
terminals and wiring must be met. The barrier must be inserted into a 4˝ Ч 4˝
Ч 2

1

/

8

˝ junction box, and the control module must be placed into the barrier

and attached to the junction box (Figure 2A). The power-limited wiring must
be placed into the isolated quadrant of the module barrier (Figure 2B).

1. Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in

Figure 2A.

IMPORTANT: When using the SK-Control for fire fighter telephone applica-
tions, remove Jumper (J1) and discard. The Jumper is located on the back as
shown in Figure 1B.

SpECIfICATIONS
Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

6.5 mA (LED on)

Average Operating Current:

375μA (LED flashing - in group poll mode) 350μA (LED flashing - in direct poll mode) 485μA Max. (LED flashing, NAC shorted)

Maximum NAC Line Loss:

4 VDC

Reg. Ext. Supply Voltage:

(between Terminals T3 and T4)

Maximum (NAC):

Regulated 24VDC

Drain on External Supply:

1.7 mA Maximum (using 24 VDC supply)

Max. NAC Current Ratings:

For class B wiring system, 3A; For class A wiring system, 2A

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

/

2

˝ H x 4” W x 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories:

SMB500 Electrical Box

fIgURE 1A. CONTROLS AND

fIgURE 1B. JUMpER LOCATION:

INDICATORS:

J1

C1059-00

C0910-00

fIgURE 2A. MODULE MOUNTINg

fIgURE 2B:

WITh BARRIER:

C1047-00

I56-3436-00

1

12 Clintonville Road, Northford, CT 06472

203.484.7161; Fax: 203.484.7118

www.silentknight.com

Advertising