Speaker Wiring

Each SKE-ZN6 supplies six Notification
Appliance Circuits for speaker connection. The
circuits can be supervised and wired Class B
(Style Y) or Class A (Style Z). Each circuit is
capable of 20 watts of power.

Note: The system can support a maximum of 50 watts of power.

1. Remove the cover plate on the SKE-ZN6.

See Figure 3.

2. To wire speakers to the control panel using

Class B (Style Y) supervision see Figure 4.

Figure 4: Class B (Style Y) Speaker Configuration

3. To wire speaker circuits to the control panel

in a Class A (Style Z) configuration see
Figure 5.

Figure 5: Class A (Style Z) Speaker Configuration

FACP Alarm Control Wiring

This section describes how to connect relay
outputs from a FACP to control the four separate
zones on the SKE-ZN6 four zone splitter.
1. Connect an active low relay or contact from

the FACP to the Alarm Selects on the SKE-
ZN6. See Figure 6.

Figure 6: FACP Alarm Control Outputs

Electrical Specifications

Supervised

Power Limited

15 k

Ω EOL

UL Listed

Model 7630

Supervised

Power Limited

Ground Fault Impedance To Any Terminal: 0

Ω

Audio Circuit: 25 Vrms or 70.7 Vrms
Standby Input Power: 27.4 VDC @ 35 mA
Alarm Input Power: 27.4 VDC @ 120 mA

Supervised

Power Limited

Non-Supervised

Power Limited

4.7 k

Ω

UL Listed EOL

Model 7628

Must be wired

within 20 feet

and in conduit