SilentKnight SK-Ion Addressable Ionization Smoke Detector User Manual

Sk-ion plug-in intelligent ionization sensor

Advertising
background image

This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
GENERAL DESCRIPTION
Model SK-Ion is an intelligent sensor that uses a state-of-the-art sensing cham-
ber. This sensor is designed to provide open area protection and is intended
for use with compatible control panels only. Two LEDs on each sensor light to
provide a local, visible sensor indication. Remote LED annunciator capability
is available as an optional accessory (Part No. RA400Z).

Please refer to the operation manual for the UL listed control unit for specific
operation of the SK-Ion.
The SK-Ion requires compatible addressable communications to function
properly. Connect this sensor to listed-compatible control panels only.
SPACING
Silent Knight recommends spacing sensors in compliance with NFPA 72. In
low air flow applications with smooth ceilings, space sensors 30 feet apart.
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide,
available from Silent Knight.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.

1. Wire the sensor base (supplied separately) per the wiring diagram, see

Figure 1.

2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base

while turning it clockwise to secure it in place.

4. After all sensors have been installed, apply power to the control unit and

activate the communication line.

5. Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during
shipment. Dust covers must be removed before the sensors can sense smoke.
Remove the sensors prior to heavy remodeling or construction.

SK-400-005

1

I56-3428-000R

FIGURE 1. WIRING DIAGRAm:

3

2

1

3

2

1

+

-

-

+

+

-

REMOTE

ANNUNCIATOR

UL

LISTED COM

P

A

TIBLE

CONTROL

P

ANEL

OPTIONAL RETURN LOOP

DO NOT LOOP WIRE

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO

PROVIDE SUPERVISION

OF CONNECTION.

C0147-00

FIGURE 2:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0146-00

TAmPER-RESISTANCE
Model SK-Ion includes a tamper-resistant capability that prevents its removal
from the bracket without the use of a tool. Refer to the base manual for details
on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when tested and maintained in compliance with
NFPA 72.

Test the sensor as follows:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

This sensor can be functionally tested with a test magnet. The test mag-
net electronically simulates smoke in the sensing chamber, testing the
sensor electronics and connections to the control panel.

1. Hold the test magnet in the magnet test area as shown in Figure 3.

2. The sensor should alarm the panel.

Two LEDs on the sensor are controlled by the panel to indicate sensor

I56-3428-000R

SPECIFICATIONS
Operating Voltage Range:

15 to 32 VDC

Maximum Average Standby Current:

300µA @ 24 VDC

Maximum Alarm Current (LED on):

6.5 mA @ 24 VDC

Operating Humidity Range:

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range:

32°F to 120°F (0°C to 49°C)

Height:

2.0˝ (51 mm) installed in B210LP Base

Diameter:

6.1˝ (155 mm) installed in B210LP Base; 4.1˝ (104 mm) installed in B501 Base

Weight:

5.4 oz. (153 g)

INSTALLATION AND mAINTENANCE INSTRUCTIONS

7550 Meridian Circle, Maple Grove, MN 55369-4927

763.493.6455, 800.328.0103; Fax: 763.493.6475

http://www.silentknight.com

SK-Ion Plug-in
Intelligent Ionization Sensor

Advertising