SilentKnight SK-Iso Line Isolator Module User Manual

Sk-iso fault isolator module, Installation and maintenance instructions

Advertising
background image

SK-460-010

1

I56-3445-001

©2009 Honeywell International Inc.

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SK-ISO Fault Isolator Module

I56-3445-00

1

SPECIFICATIONS
Normal Operating Voltage:

15-32 VDC

Stand-By Current:

450µA (not isolating, relay closed)

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

/

2

˝ H × 4˝ W ×

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box)

FAULT ISOLATOR

MODULE

1 (-)
2 (+)
3 (-)
4 (+)

UL LISTED COMPATIBLE

CONTROL PANEL

FAULT ISOLATOR

MODULE

1 (-)
2 (+)
3 (-)
4 (+)

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

SHIELDED-TWISTED PAIR

IS RECOMMENDED

GROUPS OF DEVICES ARE SEPERATED BY FAULT ISOLATOR

MODULES. ANY COMBINATION OF COMPATIBLE, LISTED

DEVICES MAY BE CIRCUIT WITHIN THAT GROUP.

A PAIR OF FAULT ISOLATOR MODULES WILL DISCONNECT A

GROUP OF DEVICES IF A SHORT CIRCUIT OCCURS ON THE

SIGNALING LINE CIRCUIT WITHIN THAT GROUP.

1 (-)
2 (+)

1 (-)
2 (+)

1 (-)
2 (+)

1 (-)
2 (+)

ALL WIRING SHOWN IS SUPERVISED.

1 (-)
2 (+)

1 (-)
2 (+)

FAULT ISOLATOR

MODULE

FAULT ISOLATOR

MODULE

1 (-)
2 (+)
3 (-)
4 (+)

1 (-)
2 (+)
3 (-)
4 (+)

FIGURE 1. SK-ISO FAULT ISOLATOR MODULE WIRING DIAGRAM

This information is included as a quick reference installation guide. Refer to
the appropriate Silent Knight Installation Manual for detailed system informa-
tion. If the modules will be installed in an existing operational system, inform
the operator and local authority that the system will be temporarily out of
service. Disconnect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
SK-ISO FAULT ISOLATOR MODULES enable part of the communications loop
to continue operating when a short circuit occurs on it. An LED indicator
blinks in the normal condition and turns on during a short circuit condition.
The module will automatically restore the entire communications loop to the
normal condition when the short circuit is removed.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to compatible
Silent Knight system control panels only.

NOTE: In general, up to 25 addressable devices may be grouped between iso-
lator modules.

MOUNTING
SK-ISO modules mount directly to 4 inch square electrical boxes. The box
must have a minimum depth of 21/8˝.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and the wir-
ing diagrams in Figure 1.
2. Secure module to electrical box (supplied by installer).

C0802-01