SilentKnight SK-Mon-10 Addressable Ten Input Monitor Module User Manual

Sk-mon-10 ten input monitor module, Installation and maintenance instructions, 2) nuts

Advertising
background image

SK-460-009

1

I56-3443-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3443-000

7550 Meridian Circle, Maple Grove, MN 55369-4927

763.493.6455, 800.328.0103; Fax: 763.493.6475

http://www.silentknight.com

SK-Mon-10 Ten Input Monitor Module

SPECIFICATIONS
Normal Operating Voltage:

15-32 VDC

Stand-By Current:

3.5 mA

Alarm Current:

55 mA (assumes all ten LEDs solid on)

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10 to 93% Non-condensing

Dimensions:

6.8˝ H x 5.8˝ W x 1.25˝ D

Accessories:

IDP-ACB Cabinet and Chassis

Wire Gauge:

12-18 AWG

Maximum IDC
Wiring Resistance:

1500 Ohms

Maximum IDC Voltage:

10.2 VDC

Maximum IDC Current:

240 µA (each circuit)

BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Mon-10 Ten Input Monitor Module is intended for use in an intelligent
alarm system. Each monitor module is intended to interface between a control
panel and normally open contact devices, such as pull stations. A common
SLC input is used for all modules, and the initiating device loops share a
common supervisory supply and ground. Otherwise, each monitor operates
independently from the others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first mod-
ule from 01 to 150 (01 to 90 on panels that support up to 99 addresses).
The remaining modules are automatically assigned to the next nine higher
addresses. Provisions are included for disabling a maximum of two unused
modules to release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the LEDs to blink,
latch on, or latch off.

C0202-00

ShIPPED ON BOARD:
(1) Shunt in Class A/B position

(Shipped in Class B position, remove shunt for Class A)

INCLUDED:
(6) 1 x 4 Terminal Blocks (2) 1

1

/

4

˝ (32mm) Stand offs

(4) Machine Screws (3) Shunts (10) 47k Ohm

End of Line Resistors

(2) Nuts

COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel.
COMPONENTS
The following is a description of the SK-Mon-10 mounting framework:

One or two SK-Mon-10 modules can be installed in an IDP-ACB cabi-

net.

The IDP-ACB cabinet has a built-in chassis that will accommodate one or two
SK-Mon-10 modules.

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

10

11

12

13

14

15

BASE

ADDRESS

ADDRESS

DISABLE

0

1

2 3 4 5 6

7

8

9

0

7

8

6

5

4

3

2

1

9

BASE

ADDRESS

ADDRESS

DISABLE

10

11

12

13

14

15

C0234-05

FIGURE 1: IDP-ACB CABINET

The front SK-Mon-10 module positions of each chassis are offset below the
rear SK-Mon-10 module positions so that all of the status indicators are visible.
For cabinet dimensions refer to the IDP-ACB instruction manual.