SilentKnight SK-Pull-DA Addressable Dual Action Pull Station User Manual

Sk-pull-da addressable pull station

Advertising
background image

SK-Pull-DA Addressable Pull Station

Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending

Document 52149

I56-3447-002

Description

The SK-Pull-DA Addressable pull station is a non-coded, dual-action manual pull station

with a key-lock reset feature. It provides Silent Knight intelligent fire alarm control panels

(FACP) with one addressable alarm initiating input. The addressable module is housed inside

the pull station. The SK-Pull-DA is compatible with all Silent Knight intelligent panels that

use the Intelligent Device Protocol (IDP). Refer to the FACP Installation Manual to determine

if Intelligent Device Protocol is supported. The SK-Pull-DA meets the ADAAG controls

and operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5

lb. maximum pull force to activate the pull station. Operating instructions are molded into

the pull station handle along with Braille text. Molded Terminal numbers are also present.

Conforms to ANSI/UL Standard 38.

Ratings

Normal Operating Voltage: 24VDC.

Average Operating Current (LED Flash): 300 µA.

Temperature Range: 32°F – 120°F (0°C – 49°C).

Relative Humidity Range: 10% - 93% non-condensing.

Installation

The SK-Pull-DA Addressable pull station can be surface mounted to a SB-I/O surface

backbox or semi-flush mounted on a standard single-gang, double-gang or 4˝ (10.16 cm)

square electrical box. The optional BG-TR trim ring can be used if the SK-Pull-DA is to

be semi-flush mounted.

Operation

To activate the dual-action pull station, push in and pull down on the handle. The word

‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta-

tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)

switch which closes upon activation of the pull station.

Resetting the Pull Station

1. Insert the key into the lock and rotate 1/4 turn counterclockwise.

2. Open the door until the handle returns to normal.

3. Close and lock the door.

P0260-00

SLC

SLC

STRIP GAUGE

1 2 3 4

From

FACP

To

Next

Addressable

Device

P0267-00

Wiring

NOTE: Closing the door automatically resets the switch to the ‘Normal’ position. Opening

the door will not activate or deactivate the alarm switch.
CAUTION! Do not detach the door of the pull station during installation. The door of

the pull station cannot be reattached to the backplate after the backplate has already been

installed onto an electrical box.

CAUTION!

Install the Silent Knight SK-Pull-DA addressable pull station in accordance with these

instructions, applicable NFPA standards, national and local Fire and Electrical codes and

the requirements of the AHJ (Authority Having Jurisdiction). Regular testing of the devices

should be conducted in accordance with the appropriate NFPA standards. Failure to follow

these directions may result in failure of the device to report an alarm condition. Silent Knight

is not responsible for devices that have been improperly installed, tested or maintained.

ADA Compliance

For ADA compliance, if the clear floor space only allows forward approach to an object, the

maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space

allows parallel approach by a person in a wheelchair, the maximum side reach allowed is

54 inches (137.16 cm).

SK-Pull-DA

Addressable Pull Station

(over for Programming information)

Document 52149 I56-3447-002