SK-460-007

1

I56-3439-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-3439-000

7550 Meridian Circle, Maple Grove, MN 55369-4927

763.493.6455, 800.328.0103; Fax: 763.493.6475

http://www.silentknight.com

SK-Relay-6
Six Relay Control Module

SPECIFICATIONS
Normal Operating Voltage:

15-32 VDC Stand-By Current:1.45 mA

Alarm Current:

32 mA (assumes all six relays have been switched once and all six LEDs solid on)

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10 to 85% Non-condensing

Dimensions:

6.8˝ H × 5.8˝ W × 1.0˝ D

Accessories:

IDP-ACB cabinet and chassis

Wire Gauge:

12-18 AWG

Relay Current:

30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control

BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.

NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Relay-6 Six Relay Control Module is intended for use in an intelligent
alarm system. Each module is intended for Form-C switching applications,
which do not require wiring supervision for the load circuit. A single isolated
set of dry relay contacts is provided for each module, which is capable of
being wired for either normally open or normally closed for each operation.
Each module has its own address. A pair of rotary code switches is used to set
the address of the first module from 01 to 94(or 01 to 154 for panels that sup-
port 159 addresses). The remaining modules are automatically assigned to the
next five higher addresses. Provisions are included for disabling a maximum
of three unused modules to release the addresses to be used elsewhere. Each
SK-Relay-6 module also has panel controlled green LED indicators. The panel
can cause the LEDs to blink, latch on, or latch off.

Contents include:.

(6) 1 × 3 Terminal Blocks
(1) 1 × 4 Terminal Blocks
(2) 11/4˝ (32mm) Stand offs
(4) Machine Screws
(2) Nuts
(1) Shunt (NOTE: For the disable position, not more than one shunt shall be

installed at the same time)

COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel.

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

.9 A

110 VDC

Resistive

Non-coded

.9 A

125 VDC

Resistive

Non-coded

.5 A

30 VDC

Inductive (L/R=5ms)

Coded

1 A

30 VDC

Inductive (L/R=2ms)

Coded

.3 A

125 VAC

Inductive (PF=.35)

Non-coded

1.5 A

25 VAC

Inductive (PF = .35)

Non-coded

.7 A

70.7 VAC

Inductive (PF=.35)

Non-coded

2 A

25 VAC

Inductive (PF=.35)

Non-coded

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.