SilentKnight SK-Zone-6 Addressable Six Zone Interface Module User Manual

Sk-zone-6 six zone interface module, Installation and maintenance instructions

Advertising
background image

SK-460-008

1

I56-3441-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-344

1-000

7550 Meridian Circle, Maple Grove, MN 55369-4927

763.493.6455, 800.328.0103; Fax: 763.493.6475

http://www.silentknight.com

SK-Zone-6
Six Zone Interface Module

SPECIFICATIONS
Normal Operating Voltage:

15-32 VDC

Stand-By Current:

2 mA

Alarm Current:

40 mA (assumes all six LEDs solid on)

Temperature Range:

32ºF to 120ºF ( 0ºC to 49ºC)

Humidity:

10 to 93% Non-condensing

Dimensions:

6.8˝ H x 5.8˝ W x 1.0˝ D

Accessories:

IDP-ACB Cabinet and chassis

Wire Gauge:

12-18 AWG

Max. IDC Wiring Resistance:

25 ohms

External Power Supply Voltage:

Regulated 24VDC

Ripple Voltage:

0.1 volts RMS maximum

IDC:

(Supervised and power limited)

DC Voltage:

18-28 volts power limited

Frequency:

DC

Current:

90mA per circuit

BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.

NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Zone-6 Six Zone Interface Module is intended for use in an intelli-
gent alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.

A pair of rotary code switches is used to set the address of the first module
from 01 to 94 (or 01 to 154 for panels that support 159 addresses). The re-
maining modules are automatically assigned to the next five higher addresses.
Provisions are included for disabling a maximum of two unused modules to
release the addresses to be used elsewhere. Each module also has panel con-
trolled bicolor LED indicators. The panel can cause the LEDs to blink, latch
on, or latch off.

DET.

MODEL

COMP. ID DETECTOR

MANUFACTURER

BASE MODEL MAX

DET.

1151

A

SYSTEM SENSOR

B110LP, B401

20

1451

A

SYSTEM SENSOR

B401, B401B

20

1451DH

A

SYSTEM SENSOR

DH400

20

2151

A

SYSTEM SENSOR

B110LP, B401

20

2451

A

SYSTEM SENSOR

DH400, B401B,
B401

20

2451TH

A

SYSTEM SENSOR

B401, B401B

20

5451

A

SYSTEM SENSOR

B401

20

1100

A

SYSTEM SENSOR

N/A

20

1400

A

SYSTEM SENSOR

N/A

20

**2100AT

A

SYSTEM SENSOR

N/A

20

2100B

A

SYSTEM SENSOR

N/A

20

2100D

A

SYSTEM SENSOR

N/A

20

2100S

A

SYSTEM SENSOR

N/A

20

2100TB

A

SYSTEM SENSOR

N/A

20

2100TD

A

SYSTEM SENSOR

N/A

20

2100TS

A

SYSTEM SENSOR

N/A

20

2300B

A

SYSTEM SENSOR

N/A

20

2300TB

A

SYSTEM SENSOR

N/A

20

2400

A

SYSTEM SENSOR

N/A

20

2400TH

A

SYSTEM SENSOR

N/A

20

*2W-B

A

SYSTEM SENSOR

N/A

20

*2W-TB

A

SYSTEM SENSOR

N/A

20

DH100LP

A

SYSTEM SENSOR

N/A

20

*Class B, Style B only; **No Accessory will be supported by 2100AT

COMPATIBLE TwO-wIRE SySTEM SENSOR SMOKE DETECTORS FOR
USE wITh SK-ZONE-6 wITh ZONE IDENTIFIER A

INCLUDED:
(5) 1 x 4 Terminal Blocks (2) 11/4˝ Stand offs (3) Shunts

(4) Machine Screws (1) Long Power Supply Jumper

(2) Nuts

(6) 3.9k Ohm

End of Line Resistors

ShIPPED ON BOARD:
(2) Shunts in Class A/B position

(Shipped in Class B position, remove shunts for Class A)

Advertising