Slant fin corp, Manual, Burner – Slant/Fin CHS-399 User Manual

Page 10: Operation, Pump

Advertising
background image

Slant Fin Corp.

Controller and Display

CHS Series

8

2.3.2 Manual Burner and Pump Operation

Figure 2-6 Manual Burner and Pump Operation Test Screens

Manual Burner Operation – test screen, allows the installer to manually control the firing rate of the burner.
Using the up and down (▲▼) buttons to highlight the menu options, and the “OK” button to select them, set
“Firing rate control” to “Manual”, then adjust “Manual firing rate” to the desired value.

Manual Pump Operation – test screen, allows the installer to manually turn the individual pumps on. Using the
up and down (▲▼) buttons to highlight the menu options, and the “OK” button to select them, set the desired
“Pump Control” to “On”.

The burner MUST be firing to initiate Manual Burner Operation.

Setting “Burner switch” to “Off” will inhibit burner operation, regardless of the operating
conditions.

When the test is complete, return the settings to “Auto” to allow the control to
automatically turn the circulators off and on and modulate the burner firing rate as needed.

Table 2-4 Manual Burner Operation Parameters

Parameter

Description

Default

Burner
Switch *

Allows the installer to manually switch the burner off and on.

On

Manual
firing rate *

Establishes the burner firing rate (blower RPM) when “Firing rate control” is set to

“Manual in Run” or “Manual in Run & Standby”. Feature may be useful as a diagnostic
tool; i.e. to test burner operating characteristic at a specific firing rate.

N/A

Firing rate
control *

Establishes the firing rate control of the boiler:

Auto (firing rate – blower RPM is controlled by the boiler control)

Manual in Run (blower RPM is set to the “Manual firing rate” setting; only when
burner is running).

Manual in Run & Standby (blower RPM is set to the “Manual firing rate” setting).

Auto

* = Password protected

Burner switch

Manual firing rate

Firing rate control

Off

1625 RPM

Auto

Manual

Burner

Operation

CH Pump Control

DHW Pump Control

Boiler Pump Control

Auto

Auto

Auto

Manual

Pump

Operation

Advertising
This manual is related to the following products: