Lynx combi boiler 42 – Slant/Fin LX-150CB User Manual

Page 42

Advertising
background image

Lynx Combi Boiler

42

CARE AND MAINTENANCE

This section must be brought to the attention of the owner by the
installer so that the owner can make the necessary arrange-
ments with a qualified service agency for the periodic care and
maintenance of the boiler. The installer must also inform the
owner that the lack of proper care and maintenance of this boiler
and any fuel burning equipment may result in a hazardous condi-
tion. Installer should discuss contents of the User’s Information
Manual (Publication LXA-UIM) with the owner.

A trained and qualified service technician should perform the
inspection listed in these instructions before each heating season
and at regular intervals.

I. GENERAL MAINTENANCE

A. Safety check, see page 38.

B. Vent and air intake system inspection

1. Check for obstruction, condensation, corrosion and

physical damage.

2. Check outside termination. Screen and louvers should be

free of any debris and must be cleaned as required.

3. Perform “Venting and Air intake System Regular

Inspection”, see page 18.

C. Piping

Check the following:
1. Water piping and accessories for leaks. Slightest leaks

should be corrected.

2. System to be full of water and pressure to remain stable at

correct setting on gauge.

3. Air-control system. Noise and air binding in radiation

should not occur.

4. Low water cutoff for operation (see instruction furnished

with unit).

D. Boiler Room Air Supply

Check air vents for continuous positive supply of air as
required. Air needs are greatest in cold weather if boiler
installation is non-direct vent method. Air vents must open and
free of obstruction.

WARNING: The flow of combustion and ventilating air to the

boiler should not be obstructed.

II. ANNUAL MAINTENANCE

It is recommended that the igniter be inspected annually and
cleaned of all contaminents and if necessary replaced.

III. INSPECTION DURING HEATING SEASON

A. Check water pressure regularly and add water slowly to

system when needed. If much water is added, venting may be
necessary. Regular loss of water from boiler system may
indicate either a system leak, or a faulty air control system, or
a faulty automatic fill valve.

B. Check venting system. See “Venting and Air Intake System

Regular Inspection” on page 18.

C. Check condensation drain trap to be full of water. Check for

deterioration of the tubing. Check that the trap is not plugged.

D. The combustion blower does not require or have provisions

for lubrication.

E. If required, lubricate the circulator as per the manufacturer’s

instruction.

IV. CLEANING

A. Heat Exchanger: In the unlikely event of flue passage or

water passage blockage, service to remedy situation must be
performed only by an authorized Slant/FIn representative.

B. Burner: In the unlikely event of blockage or deterioration,

service to remedy situation must be performed only by an
authorized Slant/Fin representative.

IF REPLACEMENT PARTS ARE NEEDED

When parts are needed, refer to boiler model and serial number
shown on the boiler name/rating plate. Refer to publication
number LXCB-10PL replacement parts for part numbers. When-
ever possible refer to the original order by number and date.

Control identification and replacement should not be attempted
by unskilled personnel. Only, simple easily - identified controls
and parts may be obtained locally. All other control and parts
should be identified by and ordered form Slant./Fin. Relief/Safety
valves must be ASME rated for the pressure and gross output of
the boiler.

For replacement parts, heating contractors should contact their
Slant/Fin boiler distributor.

Advertising
This manual is related to the following products: