StarTech.com RKPW081915 User Manual

Instruction manual, System requirements, Specifications

Advertising
background image

Instruction Manual

DE: Bedienungsanleitung - de.startech.com

FR: Guide de l'utilisateur - fr.startech.com

ES: Guía del usuario - es.startech.com

IT: Guida per l'uso - it.startech.com

NL: Gebruiksaanwijzing - nl.startech.com
PT: Guia do usuário - pt.startech.com

Manual Revision: 11/09/2011

For the most up-to-date information, please visit: www.startech.com

RKPW081915

8 Outlet PDU Power Distribution Unit 125V 15A (12A UL)

Packaging Contents

• RKPW081915 Power Distribution Unit

• Installation Guide

System Requirements

• 19” front/rear mounting rack/cabinet (EIA 310-D compliant)

• 125VAC power source

Specifications

Number of Power Outlets

8

Connectors

8 x NEMA 5-15 female

Electrical Rating

125VAC / 15A

LEDs

1 x Ground (green)

1 x Surge (red)

Operating Temperature

-5oC to 45oC (23oF to 113oF)

Storage Temperature

-25oC to 65oC (-13oF to 149oF)

Dimensions

482.6mm x 95.5mm x 42.7mm

Weight

2016g

Installation

1. The power distribution unit takes up 1U of rack space, so locate an

appropriate location on the rack and mount it against the front or

rear mounting posts.

2. Using the mounting hardware (screws, nuts, etc.) provided with

your rack or from your rack manufacturer, secure the unit to the

posts.

3. Connect the power cable from the distribution unit to a 125VAC

power source.

NOTE: It is recommended that the unit be connected directly to a main

source and not another distribution unit.

4. Toggle the “Reset” switch on the front of the unit to the ‘on’

position to energize the unit.

5. The “Surge” LED should light up to indicate surge protection

is active. The “Ground” LED should light up to indicate proper

grounding is present.

6. You may now attach your 125VAC compatible devices to the

distribution unit.

NOTE: Combined power draw from all devices should not exceed 15A,

otherwise the built-in circuit breaker will trip.

7. In the event of an overload scenario, the built-in circuit breaker

will be tripped and power to all outlets will be stopped.

8. Disconnect the problem device or all devices from the distribution

unit and toggle the “Reset” switch to turn the ports back on.

Front View

Rear View

Reset switch

Ground LED

Surge LED

NEMA 5-15 outlets

Advertising