INSTALLATION NOTE

1. GENERAL

The TII Totel Failsafe

®

TFS

®

Station Protectors consist of a

mounting base, protector module, grommet, and fitted cover
with nylon fastening nut.

The plastic base is molded with two shallow rectangular wells,
one above and one below the ground stud / binding post
(Figure 1) and mounting holes designed to fit existing
protector mounting holes when changing station protectors.

• The number of protectors that can be connected to various

size copper-insulated ground wires is listed in Table A below.

TABLE A

Ground Wire Capacity

Wire Size (AWG)

No. of Primary Protectors

12

1 to 2

10

3 to 5

6

6 or more


National Electric Code Requirement. The protector shall
be installed per National Electric Code ANSI/NFPA 70,
Article 800, Section C, and shall meet all applicable local
safety codes.

2. INSTALLATION

Precautions

Mount the station protector so as to minimize the possibility
of dirt or moisture getting into the protector.

• Station protectors mounted side-by-side or end-to-end

should be placed so covers can be easily removed. The
cover is furnished with a nylon retention nut which secures
the cover to the base (Figure 1). The cover is secured or
removed by using a 3/8” terminal wrench.

• Where protection for multiple services is required, it is

recommended that a protected building terminal in an
interior terminal box be installed in place of station
protectors.










Mounting

Mount the station protector vertically on a flat surface using
appropriate hardware (the length of the mounting screws
should allow for 1/8” of length within the protector).

The mounting holes are covered with a thin film of plastic,
easily punched out, to maintain the environmental integrity
of the protector (Figure 2).






















Wiring

Insert the grounding conductor, the customer side cable and
the telco side cable through the grommet located in the
center of the base lip.

Terminate one end of the grounding conductor (No. 6 AWG)
on the ground stud / binding post and the other end to an
appropriate ground source (Figure 3).

Terminate the Telco Side cable in between the bottom set of
washer and bottom nut of the appropriate stud (one
conductor to Tip and one to Ring) and tighten down
(Figure 3).

• Terminate the Customer Side Cable under the top set of

washers and the top nut of the appropriate stud (one
conductor to Tip and one to Ring) and tighten down
(Figure 3).

Loop back unused station wire conductors and coil around
the station wire jacket or store in such a manner as to
prevent them from coming in contact with protector
terminals or bare wires.

Protector

Ground Stud

Two Pair Wiring Scheme

Station Protector Housing

(Cover Removed)

Grounding Conductor

Figure 2

Ring Conductor

Tip Conductor

Telco Side Cable

Customer Side Cable

Mounting Hole

Protector

Figure 3

Customer Side Cable

Telco Side Cable

Cover

Retention Nut

Ground Stud / Binding Pos

t

Base

Grommet

Figure 1

Protector Modules

Protector Well