3. WIRING

3.1. Connection Diagram

3.2. The Type of Cables

The types of cables are to be determined according to the
following conditions.

• Twisted pair wires (such as those used for electronic push-

button telephone) are to be used for wiring between the
Exchange and the stations in principle.

• The number of cables pairs laid should be determined

considering the possibility of future expansion of the
system.

• Outdoor wires should be used where wiring passes through

inaccessible areas such as ceilings or under floors where
the maintenance is not performed. Indoor wires may also be
used, however, in case where there is no risk of
deterioration due to exposure to heat, etc.

Note
Specifications related to each junction are as follows.

Mini-clamp connector (N-8000EX line terminal)

Conductor diameter: ø 0.4 – 0.65 mm (AWG22 – 26),

Solid wire

Outside diameter:

ø 1.05 mm or below

Clip terminal (E-7000TB)

Conductor diameter: ø 0.4 – 0.8 mm (AWG20 – 26), Solid

wire

Outside diameter:

ø 1.5 mm or below

3.3. Relations Between Core Diameter of Cable and

Maximum Cable Length

Referring to the following chart as guidelines, design the
distance between the Exchange and stations so that loop
resistance value becomes 170 Ω or less.

3.4. Mini-Clamp Connector Connection

Mini-clamp connectors for line terminals are supplied with the
N-8000EX Exchange.
Connect the mini-clamp connector to a cable using a
commercially available tool (pliers).

Step 1. Cut off two-cable ends in equal length, and insert

them securely to a cover section (transparent side)
of the mini-clamp connector.
Note
Insert the cable without stripping the cable jacket.

Step 2. With a pair of pliers, lightly pinch the mini-clamp

cover and, after ensuring that the cable is securely
inserted, firmly squeeze on the cover.
Note
Squeeze on the mini-clamp cover until it is correctly
locked.

Step 3. Insert the wired connector (plug) into the exchange's

connector (socket) until it locks into place.

1. WALL MOUNTING

The station can be mounted on a wall using an optional
YC-290 wall mounting bracket.
The YC-290 can be installed to JIS standard one gang switch
box.

1.1. Mounting Example

Step 1. Install the YC-290 Wall mounting bracket to the wall.

Notes
• Use appropriate screws for the construction of wall.
• Wooden screws 3.5 x 20 are supplied with the

YC-290.

• No fitting screws for switch box are supplied.

Step 2. Hang the station on the Wall mounting bracket hook

to install.
Push down the station main body in the direction
indicated by the arrow.

2. DESK-TOP INSTALLATION

In desktop installations, the front operation panel can be
inclined 16˚ from the desk surface for easier operation by
attaching the YC-290 Wall Mounting Bracket to its bottom
surface.

2.1. Mounting Example

Hang the Wall mounting bracket hook on the station's wall
bracket mounting slot to install.
Push up the Wall mounting bracket in the direction indicated
by the arrow.

This Master Station is designed to connect to the IP Intercom Exchange, and provides hands-free conversation of high sound
quality. With its space-saving design, this Master Station features the same functions as the Standard Master Station.
Using an optional YC-290 Wall Mounting Bracket, this station can be mounted on a wall, or tilted for easy key operation when
used on a desktop.

Warning
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be
required to take adequate measures.

N-8011MS

STANDARD HANDS-FREE MASTER STATION

INSTALLATION MANUAL

1

2

YC-290 Wall mounting bracket

Station

Wooden screw 3.5 x 20
(supplied with the YC-290)

Hook

Wall

surface

2-ø4.5

4.6 x 6

83.5

23.5

131.5

60

50

37

50

34

64

4.5 x 10

[YC-290 Dimensional drawing]

Unit: mm

Rubber foot mounting position
(desk-top application)

92

72.1

60.7

195

YC-290

[Installation completion drawing]

YC-290

Unit: mm

YC-290 Wall
mounting bracket

Hook

Rubber foot
(supplied with
the YC-290)

Station

16

90

[Installation completion drawing]

192.3

YC-290

Unit: mm

Both upper and lower
terminals (clip terminals)
are internally connected.

E-7000TB
Terminal board

Station

Connection cable

(accessory)

RJ-11 modular rosette
(commercially available)

Mini-clamp connector
(Supplied with the N-8000EX)

To N-8000EX Exchange

16 lines

Cover (transparent side)

Cable

N-8000EX Rear panel

To connect the cables from the N-8000EX
Exchange to the Master Station, use the supplied
connection cable and a commercially available RJ-
11 modular jack. These cables have no polarity.

Conductor

diameter

(mm)

ш 0.4

ш 0.5

ш 0.65

ш 0.9

Maximum cable length between the

Exchange and station

(Assuming that the loop resistance is 170 Ω.)

570 m

900 m

1.5 km

2.9 km

Loop

resistance

(Ω/km)

295

187

113

58

133-06-260-5C