5

Installation - Domestic Piping

Temperature & Pressure (T&P) Relief Valve

To reduce risk of excessive pressures and tem-
peratures in the water heater, install tempera-
ture and pressure protective equipment
required by local codes, but no less than a com-
bination temperature and pressure relief valve
certified by a nationally recognized testing lab-
oratory that maintains periodic inspection of
production of listed equipment or materials, as
meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water
Supply Systems, ANSI Z21.22. This valve must
be marked with a maximum working pressure
of the water heater.

The Excellence water heater must be protected
with a T&P relief valve.

Size the Excellence T&P relief valve by the
following specifications, unless they conflict
with local codes: 3/4” NPT with an AGA
Rating of 100,000 BTU/hr (Watts 100XL-8 or
equivalent).

For proper operation of the T&P and to pre-
vent the T&P from activating due to boiler
water temperature, use a T&P relief valve
with extended element. A 8” minimum
length is recommended.

Standard Installation

Install T&P relief valve in the Auxiliary con-
nection located behind the air vent on the top of
the water heater as shown Fig. 2 page 8.

Commonwealth of Massachusetts Installation

Follow this procedure for jurisdictions requiring a
vacuum breaker to be installed on the domestic
cold water inlet.

Install the T&P in the run (straight through leg)
of a tee located at the domestic hot water out-
let. Use a long element T&P relief valve, as
shown in Fig. 3 page 8.

T&P Relief Valve Discharge Piping

T&P relief valve discharge piping must be:

- made of material serviceable for tempera-

tures of 250ºF or greater.

- directed so that hot water flows away from

all persons.

- directed to a suitable place for disposal.

- installed so as to allow complete draining

of the T&P relief valve and discharge line.

T&P relief valve discharge piping must not be:

- excessively long. Using more than 2

elbows or 15 feet of piping can reduce dis-
charge capacity.

- directly connected to a drain. Terminate

discharge piping within 6” from drain.
Refer to local codes.

- plugged, reduced or restricted.

- subject to freezing.

Do not install any valve between T&P relief
valve and tank connection or on T&P relief
valve discharge piping. Do not plug T&P
relief valve or discharge piping. Improper
placement and piping of T&P relief valve
can cause severe personal injury, death or
substantial property damage.

WARNING

NOTICE

CAUTION