Wilkerson P16A User Manual

Warning, Application limits, Installation

Advertising
background image

Installation & Service Instructions
83-063-000

Precision Air Pressure Regulator P16A
with Variations and Accessories

ISSUED: April, 2006
Supersedes: July, 2004

Doc.# 83063000, ECN# 060299, Rev.

4

!

WARNING

FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE
PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED
ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY
DAMAGE.
This document and other information from The Company, its subsidiaries
and authorized distributors provide product and/or system options for
further investigation by users having technical expertise. It is important
that you analyze all aspects of your application, including consequences
of any failure and review the information concerning the product or
systems in the current product catalog. Due to the variety of operating
conditions and applications for these products or systems, the user,
through its own analysis and testing, is solely responsible for making
the final selection of the products and systems and assuring that all
performance, safety and warning requirements of the application are
met.
The products described herein, including without limitation, product
features, specifications, designs, availability and pricing, are subject to
change by The Company and its subsidiaries at any time without notice.

EXTRA COPIES OF THESE INSTRUCTIONS ARE AVAILABLE FOR
INCLUSION IN EQUIPMENT / MAINTENANCE MANUALS THAT UTILIZE
THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE.

Richland, MI 49083

Tel: (269) 629-5000

Introduction

Follow these instructions when installing, operating, or servicing
the product.

Application Limits

These products are intended for use in general purpose
compressed air systems only.

Installation

1. Install the Regulator as close as possible to the application.

2. Install the unit with the air flowing through the body in the

direction indicated by the arrow.

3. Gauge ports (1/4") are provided in either side of the

regulator body for installation of a gauge or use as an
additional outlet port. Plug unused port(s). System piping
should be same size as regulator porting. In systems with a
cyclic demand, the regulator should be located upstream of
cycling device.

Operation

Maximum pressure rating is 300 psig (21 bar). Temperature
range is 32°F to 150°F (0°C to 65.5°C).

1. Before turning on the supply air pressure, turn the

regulator adjusting knob counterclockwise until there is no
load on the regulating spring.

2. Turn on the supply air pressure and then turn the adjusting

knob clockwise until the desired secondary pressure is
reached.

3. To avoid minor readjustment after making a change in

pressure setting, always approach the desired pressure
from a lower pressure.

4. When reducing from a higher to a lower setting, first

reduce to some pressure less than that desired and then
increase to the desired pressure.

Maintenance

1. The regulator can be disassembled for servicing without

removal from line.

2. Occasionally remove bottom plug and clean plug, body and

valve seat.

3. TO DISASSEMBLE — shut off air to regulator and vent air

line on both sides of regulator. Turn adjusting knob
counterclockwise to relieve compression on spring.
Remove the knob cover cap, screws, cover and spring.
Diaphragm assembly can now be removed. By removing
bottom plug and spring the valve stem can be removed
from the bottom of the regulator.

4. IF UNIT WILL NOT REGULATE TO DESIRED PRESSURE

or if pressure becomes excessive - remove bottom plug,
spring, and valve assembly. Clean all parts and check valve
seat for wear or damage. Replace worn or damaged parts.

5. If excessive air leaks continuously from relief hole, the

regulator should be taken out of service and a
recommended repair kit installed, as listed under Repair
Kits and Replacement Parts.

6. WHEN REPLACING DIAPHRAGM ASSEMBLY — The

PRP-95-960 diaphragm assembly is a relieving-type
diaphragm.

!

WARNING

To avoid unpredictable system behavior that can cause personal injury
and property damage:

Disconnect electrical supply (when necessary) before installation,
servicing, or conversion.

Disconnect air supply and depressurize all air lines connected to
this product before installation, servicing, or conversion.

Operate within the manufacturer’s specified pressure, temperature,
and other conditions listed in these instructions.

Medium must be moisture-free if ambient temperature is below
freezing.

Service according to procedures listed in these instructions.

Installation, service, and conversion of these products must be
performed by knowledgeable personnel who understand how
pneumatic products are to be applied.

After installation, servicing, or conversion, air and electrical supplies
(when necessary) should be connected and the product tested for
proper function and leakage. If audible leakage is present, or the
product does not operate properly, do not put into use.

Warnings and specifications on the product should not be covered
by paint, etc. If masking is not possible, contact your local
representative for replacement labels.

!

WARNING

Product rupture can cause serious injury.

Do not connect regulator to bottled gas.

Do not exceed maximum primary pressure rating.