40mm & 60mm Proportional Regulator

2R210

4

Set Pressure Scale

Units with NPT port threads are supplied with a factory set PSI pressure scale. Use parameter 14 to change scale to bar.

Parameter Number 14 – Set Pressure Scale in PSI or bar

Step

1

2

3

4

5

Press

3-6 seconds

Until

Display

Reads

Flashing Decimal

Flashing Decimal

Flashing

Description

Accesses

changeable

parameters.

Accesses

parameter no. 14.

Displays current

parameter value.
1 = PSI, 0 = bar

Edits parameter.

Accepts and saves

new parameter

setting.

Sequences to next

parameter.

or

or

Preset Minimum Pressure

If there is a need for a pre-set minimum pressure, use parameter 18. (Note: preset pressure is affected by % P19.)

Parameter Number 18 – Set Minimum Preset Pressure

Step

1

2

3

4

5

Press

3-6 seconds

Until

Display

Reads

Flashing Decimal

Flashing Decimal

(value between

0 and 200)

Flashing

Description

Accesses

changeable

parameters.

Accesses

parameter no.

18.

Displays current parameter value.

Incremental value is:

2 bar unit: x 2 mbar x % P19

10 bar unit: x 10 mbar x % P19

Edits parameter.

Accepts and

saves new

parameter

setting.

Sequences to

next parameter.

or

or

Set Pressure Correction

Pressure correction allows the user to set a maximum pressure as a percentage of secondary pressure F.S.
Example: If F.S. is 10 bar, set parameter 19 to 50 for maximum preset pressure of 5 bar.
Pressure correction also affects the minimum preset pressure in parameter 18.
Example: If F.S. is 10 bar and parameter 18 is set to a value of 100 (1 bar), and parameter 19 is set to 50%, then the actual
minimum preset pressure seen is 0.5 bar.

Parameter Number 19 – Set Maximum Preset Pressure

Step

1

2

3

4

5

Press

3-6 seconds

Until

Display

Reads

Flashing Decimal

Flashing Decimal

(value between

0 and 100)

Flashing

Description

Accesses

changeable

parameters.

Accesses

parameter no. 19.

Displays current

parameter value.

Incremental

value is: % of F.S.

Edits parameter.

Accepts and saves

new parameter

setting.

Sequences to next

parameter.

or

or