Winco PSS15B4W/A User Manual

Page 7

Advertising
background image

PAGE 5

4141-10

60706-168

NATURAL GAS or LP VAPOR

Size of pipe normally required for generators operating

on NATURAL GAS or LP VAPOR

up to 25 feet*

25 - 100 feet* over 100 feet*

use a two

PSS15B4W 3/4” pipe

1” pipe

regulator system

*Allow an additional 3 feet for each standard elbow. Do not use
‘street ells’ (restrictive)*

**** CAUTION ****
Be careful when sealing gas joints. Excessive sealing
compound can be drawn into the solenoid, regulator or
carburetor causing an engine malfunction.

FUEL PRESSURE

L.P. & N.G. VAPOR FUEL

Correct fuel pressure cannot be stressed enough. The

most common cause for inoperative systems is an
inadequate or incorrect fuel pressure. Performance of the
engine is in direct relation to the correctness of the fuel
system. Shown below is a block diagram of a typical L.P.
or N.G. vapor fuel installation.

Notice the following tables give two (2) different units of

measuring fuel pressure. The first and most accurate is
the use of a simple water manometer. A manometer is
calibrated in inches of water column. The second is with a
pressure gauge calibrated in ounces per square inch.

Reference numbers 1 through 3 in the block diagrams

above are system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each

reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only)

1

3 4

UNIT OFF

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only)

1

2

3

4

UNIT OFF

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD TANK PSI

10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz

Natural Gas

1

3

4

UNIT OFF

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

FULL LOAD LINE PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

LP/NG FUEL CONVERSION

The PSS15B4W/A generator systems have been

tested on NATURAL GAS prior to shipment. If you are
going to use them on LP vapor, follow the procedures
outlined below to change the fuel type.

1. Connect your LP supply to the unit, making sure
that you have the correct fuel pressure.

2. Locate the vapor fuel adapter mounted between
the air filter and the carburetor body.

Advertising