PAGE 11

8009-30

60706-184

5. About 15 seconds after the generator (alternate
source) acceptable light comes on, the automatic
transfer switch should transfer the load from the utility
to the generator. At that time the Transfer Switch on
generator light should come on.

6. The generator will stay connected to the load for
about 5 minutes at which time the transfer switch will
transfer the load back to the utility. At the time it
transfers back to utility the Transfer Switch on Utility
light should come on and the Transfer Switch on
generator light should go out. To bypass this five
minute time delay you can press and release the
Push to Test button again at any time.

7. After the load retransfers to the utility the generator
will continue to run for about 1 minute (without a load)
and then shut down. The Generator acceptable light
will go off indicating the generator set has shut down.

Once you are finished testing the transfer switch, this
completes your installation and unit testing. ALWAYS
leave the system in automatic mode unless servicing the
unit. For automatic operation, keep the generator set
mode switch in the “AUTOMATIC” position.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to
automatically exercise the generator for 20 minutes once
every fourteen days .

SETTING THE EXERCISER CIRCUIT

Press and release the Automatic Generator Exerciser
button. After about 8 seconds the exerciser light flashes
14 times to indicate that the exerciser circuit has been
set. The number of flashes indicates the number of days
until the next exercise period. This 20 minute period will
occur at approximately the same time of the day the
button was pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the Automatic Generator Exerciser
button until the light above the button goes off, the light
flashes and then goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the Automatic Generator Exerciser
button until the light goes off, the light flashes then goes
off. After about 8 seconds the exerciser light flashes
fourteen times to indicate that the exerciser circuit has
been re-enabled.

*************
***** WARNING *****
*************
WITH A TOTAL POWER FAILURE (UTILITY POWER
FAILS AND THE GENERATOR FAILS TO START AND
RUN) THE EXERCISER MUST BE RESET AFTER THE
POWER IS RESTORED.

Once you are finished testing the transfer switch, this
completes your installation and unit testing. ALWAYS
leave the system in automatic mode unless servicing the
unit. For automatic operation, keep both the generator set
and transfer selector switches in the “AUTOMATIC”
position.