3.7 CURRENT SENSING


Measurement type

True RMS conversion

Sample Rate

5KHz or better

Harmonics

Up to 10

th

or better

Nominal CT secondary rating

1A or 5A (5A recommended)

Maximum continuous current

5A

Overload Measurement

3 x Nominal Range setting

Absolute maximum overload

50A for 1 second

Burden

0.5VA (0.02Ω current shunts)

common mode offset

±2V peak plant ground to CT common terminal

Resolution

0.5% of 5A

Accuracy

±1% of Nominal (1A or 5A) (excluding CT error)