DSE Model 7000 Series Control & Instrumentation System Operators Manual

Part No. 057-074 7000 Series OPERATING MANUAL ISSUE 5 15/10/2009 ADM

55








NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of the

controllers digital inputs.
3) Digital input configured for “Generator closed auxiliary” – The LED illuminates when the generator

closed auxiliary input is active – The LED shows the state of the auxiliary contact.

4) There is NO input configured for “Generator closed auxiliary” (factory default setting) – The LED

illuminates when the 7x20 gives the loading signal to the generator – The LED shows the state of the
7x20’s loading request.

NOTE:- “Mains on load” LED has two modes of operation depending upon the configuration of the

controllers digital inputs.
5) Digital input configured for “Mains closed auxiliary” – The LED illuminates when the mains closed

auxiliary input is active – The LED shows the state of the auxiliary contact.

6) There is NO input configured for “Mains closed auxiliary” (factory default setting) – The LED illuminates

when the 7x20 gives the loading signal to the mains – The LED shows the state of the 7x20’s loading
request.

Close Generator LED.
On When The Generator
Is Required To Be On
Load.

Generator
Available
LED.
On when the
generator is
within limits
and able to
take load.

Mains Available
LED.
On when the
mains is within
limits and able to
take load.

Close Mains LED.
On When The Generator
Is Required To Be On
Load.